Configuration7-948XX/49XXSHB03997.1.1.7 Limitation of the speed set-valueMain and additional set-values are lined via the arithmetic block 1 and then
Configuration7-1048XX/49XXSHB03997.1.2 Actual value feedback7.1.2.1 Armature voltage feedbackIn speed control with armature voltage feedback, the actu
Configuration7-1148XX/49XXSHB03997.1.2.2 DC voltage tacho feedbackThe actual speed value is fed back via X1/3 and X1/4. The tacho signal isconditioned
Configuration7-1248XX/49XXSHB0399Note!If the field terminals (I, K) or the polarity of the actual value encoder is reversed(resolver, tacho), a TRIP m
Configuration7-1348XX/49XXSHB03997.1.2.3 Resolver feedbackWith the following configurations of C005, a resolver can be used as speed orphase feedback
Configuration7-1448XX/49XXSHB03997.1.3 Adaptation and adjustment fo the control circuit parameters7.1.3.1 Adaptation of the armature time constantIf t
Configuration7-1548XX/49XXSHB03997.1.3.3 Field controller adjustmentStop!With field weakening operation, the motor speed can be so high that the motor
Configuration7-1648XX/49XXSHB0399Rating to detect IFminWith the parameter IFmin(C231), thespeed setting rangeislimited so that operationat impermissib
Configuration7-1748XX/49XXSHB0399Adjustment of the field weakening operation:1. Enter IFminunder C231 (10...100% ref. to IFrated).2. Selection of 100%
Configuration7-1848XX/49XXSHB0399( VabcontrolThe field weakening operation is derived from the control level of the Vdowncontroller. With this control
EDS4900U--A00408849ManualPart AContentsPreface and general informationSafety informationDC speed controller4800/4900Show/Hide Bookmarks
Configuration7-1948XX/49XXSHB0399C072 Kdnspeed controllerFor an improved starting behaviour of high-level controls, it is possible to set adifferentia
Configuration7-2048XX/49XXSHB0399Code NamePossible settingsLenze Selection InfoC025¤ Inputselection:Inputadjustment2 -1- Terminals X1/1, X1/2-2- Termi
Configuration7-2148XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC029¤ Automaticadjustmentfor C025100% This applies to all configu
Configuration7-2248XX/49XXSHB03997.1.5 Freely assignable inputs and outputs7.1.5.1 Freely assignable digital inputs (FDI)Change of the function assign
Configuration7-2348XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C115*] Priority forC112-0- Deactivate terminal function, if term
Configuration7-2448XX/49XXSHB03997.1.5.2 Freely assignable digital outputs (FDO)13 freely assignable digital outputs are available. 5 FDOs are in form
Configuration7-2548XX/49XXSHB0399LECOM code for FDOThe states of the FDOs can be displayed in binary format in C151 or they can beread out in HEX form
Configuration7-2648XX/49XXSHB0399Code NamePossible settingsLenze Selection InfoC116*¤ Inputselection:Freelyassignabledigitaloutput1 -1- FDO 1-2- FDO 2
Configuration7-2748XX/49XXSHB0399Signal flow Function4900SStr118A1ThresholdC017nactnact nxThreshold adjustable under C017 from -5000rpm...+ 5000rpm.H
Configuration7-2848XX/49XXSHB0399Signal flow Function4900SStr125C116/C117IAThresholdC244ÜIA IxThreshold adjustable from 0 to 100% under C244Hysteresi
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Configuration7-2948XX/49XXSHB03997.1.5.3 Freely assignable “analog” inputs (FAI)Term inal 8Term inals 1, 2Term inal 6Term inals 3, 4M otor potentiom e
Configuration7-3048XX/49XXSHB0399Normalization of digital frequency inputsIf the digital frequency inputs X5 and X9 are not assigned to the function s
Configuration7-3148XX/49XXSHB0399Code NamePossible settingsLenze Selection InfoC145*¤ Inputselection:Analogsignal1 -1- Input terminals X1/1, X1/2-2- I
Configuration7-3248XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C146*] Functionfor C145-0- No function-1- Main setpoint of C046-
Configuration7-3348XX/49XXSHB03997.1.5.4 Freely assignable monitor outputsThe controller is equipped with two analog (terminals 62 and 63) and a digit
Configuration7-3448XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C111*] Signal forC110-0- No signal-1- Main set-value (C046), ref
Configuration7-3548XX/49XXSHB0399Example for the assignment of a monitor output terminal 62 to the terminal signalC046 ”main set-value”.( C110 = -1- M
Configuration7-3648XX/49XXSHB0399Adaptation of the signal at the digital frequency output X8If another signal than stated in the basic configuration (
Configuration7-3748XX/49XXSHB03997.2 Torque control with speed limitationPurposeThe drive is changed to torque control by the setting the configuratio
Configuration7-3848XX/49XXSHB03994900Str040-+21C 047C 050+C 05140424341+C 145/C 146C 025/C 02734±180 VC27 C28C 25/C 26Enc.const.C 025/C 027-ABQSPC 070
Preface and general information1-148XX/49XXSHB03991 Preface and general information1.1 About these Operating Instructions ...- These Operating Instruc
Configuration7-3948XX/49XXSHB03997.3 Digital frequency couplingGeneral description of the systemThe digital frequency coupling described here enables
Configuration7-4048XX/49XXSHB03997.3.1 MasterPurposeThe master configuration C005 = -52- or -53- is:( to activate the phase controlwhich is preconnect
Configuration7-4148XX/49XXSHB03994900Str041-21JOG 1JOG 2JOG xE4 E501±1C041CW /CCW21 22QSPExExC134QSPC012 TC013 TirifC190E3016-1 0 V ...+ 1 0 V+8-1 0
Configuration7-4248XX/49XXSHB0399QSP at the masterIf QSP is switched at the master drive, the set-value (C050) is reduced along theQSP ramp for all dr
Configuration7-4348XX/49XXSHB03994900Str042X7 X5X8X1 X9SW IRX7 X5X8X9RX7 X5X8X9Rj, n -c trl.EncoderoutputResolverIncrem entalencoderM aster drive w it
Configuration7-4448XX/49XXSHB03994900Str043-±1C04121 22C105cw /ccwC 050+C 051nact62636263C 027 C 028C025/C026Enc.const.D ig_In_1X7QSPC 070 VC 071 TC 0
Configuration7-4548XX/49XXSHB0399Set-value conditioning of the slaveThe value read from Dig_In_2 (X9) forms the set-value (speed and phase) for theint
Configuration7-4648XX/49XXSHB03997.3.3 Slave for digital frequency cascadePurposeWith configuration C005 = -72- for the set-value cascade( the phase c
Configuration7-4748XX/49XXSHB03994900Str045-±1C04121 22C105CW /CCWC 050+C 051nactX7QSPC 070 VC 071 TC 072 KpnnndnC 056C 063C 022, C 023IC 042QSPX8C 03
Configuration7-4848XX/49XXSHB0399Cascading factorThe cascading factor directly influences the set-value at the input Dig_In_1 (X5).Encoder adaptation
Preface and general information1-248XX/49XXSHB03991.3 48XX/49XX controller1.3.1 Labelling- Lenze 48XX/49XX controllers are unambiguously designated by
Configuration7-4948XX/49XXSHB0399lead to phase errors occur.The direction changeover can, for instance, be usedfor electrical shafts, consisting of 2
Configuration7-5048XX/49XXSHB03997.3.4 Digital frequency outputDF output at the masterThe following formula applied to the DF output:Output frequency=
Configuration7-5148XX/49XXSHB03997.3.5 Speed synchronismSelectionFor speed synchronising, select the following slave configurations together withthe m
Configuration7-5248XX/49XXSHB03997.3.6 Phase synchronisationPurpose( Drive concept for positive movements(e.g. packaging of bottles on conveyor belts)
Configuration7-5348XX/49XXSHB03997.3.6.1 Phase controller+-C 254C 0501 .8 · C 0 1 1++++VpwC 255C 257 C 252C 253C 256++Set phase integratorF o llo w i
Configuration7-5448XX/49XXSHB03997.3.6.2 Phase trimmingThe phase trimming can be changed and displayed under C256.( Code C256 can be accessed via anal
Configuration7-5548XX/49XXSHB03997.4 Additional control functions7.4.1 Redundant actual value feedbackPurposeIn the event of a failure of the actual s
Configuration7-5648XX/49XXSHB0399Activation of redundant encoder feedbackThe redundant encoder feedback is activated by a change of the monitoring, ”S
Configuration7-5748XX/49XXSHB03997.4.2 Changeable parameter setsUp to four different parameter sets can be created, for instance, to processdifferent
Configuration7-5848XX/49XXSHB0399The transfer of all parameter in rising sequence of code numbers is only possibleif- the parameter used to determie t
Preface and general information1-348XX/49XXSHB03991.3.3 Legal regulationsLiability- The information, data and notes in these Operating Instructions me
Configuration7-5948XX/49XXSHB0399When the function ”load parameter set” is activated, the controller cannot react onany other signal for approx. 1 sec
Configuration7-6048XX/49XXSHB03997.4.3 4Q / 2Q changeoverPurposeWithachangeto2Q,thearmaturevoltage VAcan be set to 1.15 ¼ Vratedinstead of1.05 ¼ Vrate
Configuration7-6148XX/49XXSHB03997.4.4 Standstill excitation (field heating)PurposeWith this function, a reduced field current can be set as field hea
Configuration7-6248XX/49XXSHB03997.4.5 Control of a holding brakePurposeControl singal for holding brakes in:( hoists( travelling drives( active loads
Configuration7-6348XX/49XXSHB0399Configuration C005 = -12-, -13- (digital actual value encoder)The phase controller is overlayed under the following c
Configuration7-6448XX/49XXSHB03997.4.5.1 Engage brakeThe setting of QSP activates the function for the control of a holding brake. Thespeed set-value
Configuration7-6548XX/49XXSHB03997.4.5.2 Open brake (release)CW/CCW enable deactivates the internal controller inhibit immediately. At thesame time, t
Configuration7-6648XX/49XXSHB03994900Str052ttttttC trl. enablenField currentsetCW /CCWBrake disengagem enttim e C 1 9 6Arm ature currentBrakeH o ld i
Configuration7-6748XX/49XXSHB03997.5 Additional function blocks7.5.1 Process controllerDescriptionThe process controller is designed as independent fu
Configuration7-6848XX/49XXSHB03994900Str054VpVpVp (C222)Vp2 (C 325)Vp (C222)Vp2 (C 325)Vp3 (C 326)C 22210C 223nC 224vTTpV-C332 TC333 TirifC334 TC335 T
Preface and general information1-448XX/49XXSHB03991.4 EC Directives/Declaration of Conformity1.4.1 What is the purpose of EC directives?EC directives
Configuration7-6948XX/49XXSHB03992. Digital inputsThe digital inputs of the process controller ”Deactivate process controller”,”Switch-off I component
Configuration7-7048XX/49XXSHB03997.5.2 Arithmetic blocksPurposeWith the arithmetic blocks two different signals can be arithmetically connected tomeet
Configuration7-7148XX/49XXSHB0399ExampleThe analog inputs terminal 8 and terminal 6 are to be connected (division) via thearithmetic block 2 and then
Configuration7-7248XX/49XXSHB0399Arithmetic block 2Code NamePossible settingsCodeNameLenze Selection InfoC191*¤ Arithmeticblock 21 -0- Output = C338-1
Configuration7-7348XX/49XXSHB03997.5.3 Motor potentiometerPurposeThe motor potentiometer serves as alternative set-value source which can becontrolled
Configuration7-7448XX/49XXSHB0399If the motor potentiometer acts on the main set-value C046, QSP, the rampfunction generator of the main set-value, JO
Configuration7-7548XX/49XXSHB0399InitialisationWhen switching off the mains, the output value of the motor potentiometer isstored in the EEPROM. Selec
Configuration7-7648XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC260* Upper motorpotentiometerlimit100% -100.0 % {0.1 %} +100.0
Configuration7-7748XX/49XXSHB03997.5.4 Fixed set-valuePurposeThe function block ”fixed set-values” is used to program a maximum of 15 fixedsetpoints a
Configuration7-7848XX/49XXSHB03997.5.5 Absolute value generatorPurposeBipolar signals can be converted into unipolar signals.Parameter setting4900Str0
Preface and general information1-548XX/49XXSHB0399EC Declaration of Conformity ’99for the purpose of the EC Low Voltage Directive (73/23/EEC)amended b
Configuration7-7948XX/49XXSHB03997.5.6 Limitation elementsPurposeThe controller provides two limitation elements. With these function blocks signalsca
Configuration7-8048XX/49XXSHB03997.5.7 PT1 elementPurposeSignals can be filtered with this function block.Parameter setting4900Str064C 146/C 147 C 145
Configuration7-8148XX/49XXSHB03997.5.8 AdditionPurposeThe controller provides two addition facilities with three inputs each. Here, analogsignals can
Configuration7-8248XX/49XXSHB0399Addition 1:Code NamePossible settingsCodeNameLenze Selection InfoC610* Input 1,additionblock 10% -100.0 % {0.1 %} 100
Configuration7-8348XX/49XXSHB03997.5.9 Square-wave generatorPurposeThe square-wave generator accepts jump responses from the control circuits.Paramete
Configuration7-8448XX/49XXSHB03997.5.10 Dead-band elementPurposeThe dead-band element is used to set interferences around the zero point (e.g.interfer
Configuration7-8548XX/49XXSHB03997.5.11 DT1 elementPurposeThe DT1 element is to differentiate signals.It can, for instance, be used for acceleration c
Configuration7-8648XX/49XXSHB03997.5.12 Freely assignable comparatorThe freely assignable comparators generate a digital output signal which dependson
Configuration7-8748XX/49XXSHB03994900Str076t200 %0-2 0 0 %tttC om paratorinput 2H ysteresisC om paratorinput 1ResetsignalOutputsignalhigh-activeOutpu
Configuration7-8848XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC580* Input 1,Comparator 10% -100.0 % {0.1 %} +100.0 %-200 % {1
Preface and general information1-648XX/49XXSHB03991.4.4 EC Directive Electromagnetic Compatibility(89/336/EEC)amended by: First Amendment Directive (9
Configuration7-8948XX/49XXSHB03997.6 Additional control functions7.6.1 Additional torque valuesStop!The external torque limitation has an effect on th
Configuration7-9048XX/49XXSHB0399If the inputs are not assigned, constant values can be assigned via the inputcodes. These values can also be stored i
Configuration7-9148XX/49XXSHB0399Therefore, the current limitation must be reduced depending on thecompensation of the DC machine and the actual speed
Configuration7-9248XX/49XXSHB0399Code NamePossible settingsLenze Selection InfoC310* Speed-dependentcurrent limitationLimit value 1100% 0.0 % {0.1 %}
Configuration7-9348XX/49XXSHB03997.6.3 n controller adaptationPurposeThe adaptation of the speed controller is to improve the control behaviour. It is
Configuration7-9448XX/49XXSHB03997.6.4 S-shaped ramp function generator characteristicFor the ramp generator of the main set-value you can select two
Configuration7-9548XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection Info[C198*] Enableactualspeed filter0 -0- Filter not active-1- Filt
Configuration7-9648XX/49XXSHB03997.7 MonitoringNote!Fault messages can only be reset, when the fault has been eliminated.7.7.1 Change of the monitorin
Configuration7-9748XX/49XXSHB0399Message with pulse inhibitIn the event of a failure the ignition pulses are only inhibited for the armature circuit,t
Configuration7-9848XX/49XXSHB0399Changeover of the monitoring function with active TRIPEven if a monitoring function has activated a TRIP, which is st
Preface and general information1-748XX/49XXSHB0399EC Declaration of Conformity ’97 for the purpose of the EC Directiveon Electromagnetic compatibility
Configuration7-9948XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC119*¤ Selection ofmonitoringfunction-15- OC5-16- OC6-22- OUE-3
Configuration7-10048XX/49XXSHB03997.7.2 Overload monitoring for the controller (I¼t monitoring)The I¼t monitoring is designed for 150 % rated current.
Configuration7-10148XX/49XXSHB03997.7.3 Overload monitoring for the motor (I2¼tmonitoring)The unit can approximately calculate and monitor the motor t
Configuration7-10248XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC085*¤ Thermalmotor timeconstant1.0min1.0 min {0.1 min} 100.0
Configuration7-10348XX/49XXSHB03997.7.4 Blocking protection for the motorPurposeThe blocking protection avoids that the collector of the DC motor is o
Configuration7-10448XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC119*¤ Selection ofmonitoringfunction-15- OC5-16- OC6-22- OUE-
Configuration7-10548XX/49XXSHB03997.7.5 Mains monitoringPurposeThe monitoring ensure faultfree mains operation. In the event of mains failures itis no
Configuration7-10648XX/49XXSHB0399C237 = 1Short synchronisation fault do not result in pulse inhibit. This procedure should beused under the condition
Configuration7-10748XX/49XXSHB03997.7.6 Monitoring of the serial interfaceThe controller detects an interruption because incoming telegrams are notrec
Configuration7-10848XX/49XXSHB03997.8 Parameter setting( With the parameter setting of the controller you can adapt the drive to yourapplication.( The
Manual 4800 / 4900Part Content NotesATable of contentsATableofcontentsPreface and general information-PrefaceandgeneralinformationSafety information-B
Preface and general information1-848XX/49XXSHB0399Generic standards considered for the test of noise emission:Basic standard Tes t Limit valueEN 61000
Configuration7-10948XX/49XXSHB03997.8.2 Functions of the operation unit4900Str087FIG 7-60 Front view: Operating unit with status displayLEDColour Func
Configuration7-11048XX/49XXSHB03997.8.3 Structure of the operating programmeThe parameters are set in two operating levels -the code leven and the par
Configuration7-11148XX/49XXSHB03997.8.4 Basics for operation7.8.4.1 Parameter change via a codeNote!If changed parameter sets are required after mains
Configuration7-11248XX/49XXSHB0399Acceptance with SH + PRGThe controller accepts the changed parameter only after pressing SH+PRG.1. Select a code usi
Configuration7-11348XX/49XXSHB03997.8.4.2 Parameter change via two codesSome setting are parameterised via two codes:1. Select the parameter to be cha
Configuration7-11448XX/49XXSHB03997.8.4.3 Store parameter set(see chapter 7.4.2)The parameter must be stored to ensure that the setting will not be lo
Configuration7-11548XX/49XXSHB0399Via terminal controlWith terminal control it is possible to change to other parameter sets via the digitalinputs.- A
Configuration7-11648XX/49XXSHB03997.8.5 Operating modesThe controller can be adapted to your application in different ways:Terminals: The terminals ar
Configuration7-11748XX/49XXSHB03997.8.6 Display functionsCode setThe factory setting is the display of the standard code set.The extended code set is
Configuration7-11848XX/49XXSHB0399Switch-on displayAfter switching on the controller, C083 is displayed first (field current). To changethe switch-on
Preface and general information1-948XX/49XXSHB03991.4.5 EC Machinery Directive(89/392/EEC)amended by: First Amendment Directive (91/368/EEC)Second Ame
Configuration7-11948XX/49XXSHB03997.9 Code tableHow to read the code table:Column Abbreviation MeaningCode C013 Code C013The parameter value is accept
Configuration7-12048XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C005*] Configuration11 Speed control with additional setpoint-1
Configuration7-12148XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC011 nmaxspeed3000rpm250 rpm {1rpm} 5000 rpm nmaxis the referenc
Configuration7-12248XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC026¤ Encoderconstant forC0250mV C025 = -1-, -2-, -3-, -4-:Offse
Configuration7-12348XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC029¤ Automaticadjustment forC025C025 = -10-, -11-:Adjustment of
Configuration7-12448XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC043*¤ TRIP reset -0- Read: no faultWrite: reset fault-1- Read:
Configuration7-12548XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC065 Fault indication:messageDisplay Meaning--- no messageEEr ex
Configuration7-12648XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC067 Fault indication:TRIPDisplay Meaning--- no fault at present
Configuration7-12748XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC069 Controller state Bit Meaning0 Operation error1 Communicatio
Configuration7-12848XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC088 Rated motorcurrent0 A {0.1A} 100 A100 A {1A} 3600 ARated cu
Preface and general information1-1048XX/49XXSHB0399Show/Hide Bookmarks
Configuration7-12948XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C111*] Signal for C110-0- No signal-1- Main setpoint (C046), re
Configuration7-13048XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC112*¤ Input selection:Freelyassignabledigital input1 -1- digita
Configuration7-13148XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C117*] Function forC116-0- No function-1- nact nxC017 (FDO1)-2
Configuration7-13248XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC123 Currentthreshold forblockingprotection forC1240.95Irated0 A
Configuration7-13348XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC145*¤ Input selection:Analog signal1 -1- Input terminals X1/1,
Configuration7-13448XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeName[C146*] Function forC145-0- No function-1- Main setpoint of C046
Configuration7-13548XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC148 Additionaltorque value 10 -100.0 % Mmax{0.1%} + 100.0 % Mma
Configuration7-13648XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC192*¤ Input selection:Fixed setpoint1 -1- Selection fixed setpo
Configuration7-13748XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC231* Min. fieldcurrent100% 10 % IFrated{1% IFrated} 100% IFrate
Configuration7-13848XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC257* Speed trimming 0rpm -5000 rpm {1} + 5000 rpm Fixed speed o
Safety information2-148XX/49XXSHB03992 Safety informationSafety and application notes for controllers(to: Low-Voltage Directive 73/23/EEC)1. GeneralDu
Configuration7-13948XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC273* Digital/analogconversion 2-16384 {1} 16384 Input: Value fo
Configuration7-14048XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC320* Vp2of the n-controlleradaption8 1 {1} 1000 Second gain fac
Configuration7-14148XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC336* Actual Vpof theprocesscontroller0.1 {0.1} 500.0 Display: A
Configuration7-14248XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC590* Input 1,comparator 20% -100.0 % {0.1 %} + 100.0 %-200 % {1
Configuration7-14348XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC610* Input 1, additionblock 10% -100.0 % {0.1 %} 100.0 %-200 %
Configuration7-14448XX/49XXSHB0399Code Possible settingsNameCodeInfoSelectionLenzeNameC641* Input,PT1 element0% -100.0 % {0.1 %} 100.0 %-200 % {1 %} +
Configuration7-14548XX/49XXSHB03997.10 Table of attributesThe information given in this attribute table is required for generating aprogrammme. It con
Configuration7-14648XX/49XXSHB0399Code Index Data Accessdec hex DS DA DT Format DL S/P LCM-R/WAIF-PZDC000 24575 5FFFh E 1 FIX32 VD 4 P Ra -C001 24574
Configuration7-14748XX/49XXSHB0399Code AccessDataIndexAIF-PZDLCM-R/WS/PDLFormatDTDADShexdecC085 24490 5FAAh E 1 FIX32 VD 4 P Ra/W -C087 24488 5FA8h E
Configuration7-14848XX/49XXSHB0399Code AccessDataIndexAIF-PZDLCM-R/WS/PDLFormatDTDADShexdecC189 24386 5F42h E 1 FIX32 VD 4 S Ra -C190 24385 5F41h E 1
Safety information2-248XX/49XXSHB03992.1 Persons responsible for the safetyOperator( An operator is any natural or legal person who uses the drive sys
Configuration7-14948XX/49XXSHB0399Code AccessDataIndexAIF-PZDLCM-R/WS/PDLFormatDTDADShexdecC311 24264 5EC8h E 1 FIX32 VD 4 P Ra/W -C312 24263 5EC7h E
Configuration7-15048XX/49XXSHB0399Code AccessDataIndexAIF-PZDLCM-R/WS/PDLFormatDTDADShexdecC630 23945 5D89h E 1 FIX32 VD 4 P Ra/W -C631 23944 5D88h E
Configuration7-15148XX/49XXSHB0399Show/Hide Bookmarks
Configuration7-15248XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--E00408854ManualPart ETroubleshooting andfault eliminationMaintenanceDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Troubleshooting and fault elimination8-148XX/49XXSHB03998 Troubleshooting and fault eliminationWarning!During troubleshooting, the drive should always
Troubleshooting and fault elimination8-248XX/49XXSHB0399RDYIn general, the RDY message will be reset if the machine cannot generate a torquewhen runni
Troubleshooting and fault elimination8-348XX/49XXSHB03998.2 Fault analysis with the history bufferWith the history buffer, faults can be traced. The f
Troubleshooting and fault elimination8-448XX/49XXSHB03998.3 Fault messagesNote!If the fault message is interrogated by a fieldbus, the fault message i
Safety information2-348XX/49XXSHB03992.2 General safety information( These safety notes do not claim to be complete. In case of questions andproblems
Troubleshooting and fault elimination8-548XX/49XXSHB0399Display RemedyCauseOUE Mains overvoltage Mains voltage > 460V or 550V (500V variant) Reduce
Troubleshooting and fault elimination8-648XX/49XXSHB03998.4 Reset of fault indicationsTRIPAfter eliminating the fault, pulse inhibit will only be rese
Troubleshooting and fault elimination8-748XX/49XXSHB03998.5 Checking the drive systemNote!The measurements should be made with a digital voltmeter. Th
Troubleshooting and fault elimination8-848XX/49XXSHB03998.5.2 Checking the controllerChecking the power stageWarning!( The measurements described must
Maintenance9-148XX/49XXSHB03999 Maintenance9.1 Maintenance- The controller is free of maintenance if the prescribed operating condi-tions are maintain
Maintenance9-248XX/49XXSHB0399Show/Hide Bookmarks
Maintenance9-348XX/49XXSHB0399Show/Hide Bookmarks
Maintenance9-448XX/49XXSHB0399Show/Hide Bookmarks
11-148XX/49XXSHB039910 DC-bus connection11 Application of brake unitsThis chapter is part of the Lenze documentation structure.For 48XX/49XX DC contro
EDS4900U--H00408856ManualPart HAutomationDC speed controller4800/4900Show/Hide Bookmarks
Safety information2-448XX/49XXSHB03992.4 Layout of the safety information( All safety information given in these Operating Instructions has the samela
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Automation12-148XX/49XXSHB039912 Automation48XX/49XX controller can communicate with, for instance superimposed hosts(PLC or PC) as well as operating
Automation12-248XX/49XXSHB0399The operating state of the controller is indicated under C068. angezeigt.Bit No. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0Si
Automation12-348XX/49XXSHB039912.4 Enable LECOM interfaceUse fieldbus connection modules, e.g. InterBus or PROFIBUS, to integrate thecontroller in mor
Automation12-448XX/49XXSHB0399The following is available:Proass output datato besent from the controller to thecommmunicationinterface:( Mains status
Automation12-548XX/49XXSHB039912.4.2 High precision set and actual valuesSelect high precision set and actual values with a resolution of 14 bit plus
Automation12-648XX/49XXSHB0399C392 field current set-valueNote!The field current cannot be reduced more than to the minimum field current setunder C23
Automation12-748XX/49XXSHB0399Show/Hide Bookmarks
Automation12-848XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--I00408857ManualPart IAccessories and motorsDC speed controller4800/4900Show/Hide Bookmarks
EDS4900U--B00408850ManualPart BTechnical DataInstallationDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Accessories13-148XX/49XXSHB039913 AccessoriesFor the controllers, Lenze offers the following accessories (to be orderedseparately):( Mains chokes( RFI
Accessories13-248XX/49XXSHB039913.1 FusesNote!The fuses protect the controller from impermissible operating conditions. After aprotection function has
Accessories13-348XX/49XXSHB039913.1.1 Mains fusesStop!An additional cable protection is required when using fuses of the operating classaR (partial ch
Accessories13-448XX/49XXSHB039913.1.2 Armature fusesArmature fuses protect the thyristors of the controller from feedback of the motorin generator mod
Accessories13-548XX/49XXSHB039913.1.3 Internal fusesExcept for the cell fuses, all fuses are on the board 4902/3/5 LP or 4X08/11 LP.TypeRated dataOrde
Accessories13-648XX/49XXSHB0399321506,510711,51939544900Str089FIG 13-2 Fuse holder order No.: EFH300054900Str090FIG 13-3 Insulating base order No: EFZ
Automation13-748XX/49XXSHB039913.2 Mains chokesThe following mains chokes are for operation with mains voltages up to #550V+0%.13.2.1 Mains chokes for
Automation13-848XX/49XXSHB0399fmcadbnek4900Str092FIG 13-6 Mains chokes with connection lugTypeFIG a b c d e f k m n4902 FIG 13-5 120 65 109 51 162 110
Automation13-948XX/49XXSHB0399kedbnafcm4900Str093FIG 13-7 Mains choke for separate supply of the field bridgeType a b c d e f k m n4902 ... 4903 66 67
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Automation13-1048XX/49XXSHB039913.3 Pre-assembled Lenze system cable13.3.1 Resolver connection cableDesign Length [m] Order designation5 EWLR005GM10 E
Automation13-1148XX/49XXSHB039913.3.2 Incremental encoder connection cableDesign Length [m] Order designation2.5 EWLE002GM-T5 EWLE005GM-T10 EWLE010GM-
Automation13-1248XX/49XXSHB039913.4 RFI filter13.4.1 RFI filter for power connectionType Irated[A] Pv[W] Vmaxm[kg] Order designation4902 16 12 4.0 EZF
Automation13-1348XX/49XXSHB0399L1 L3L1 L3LINEL2LOADL2abfedcg12hjmkn14900Str097FIG 13-11 RFI filter, design BTypeDesign a b c d e f g h i k m n[mm2]490
Automation13-1448XX/49XXSHB039913.4.2 RFI filter for fan supplyThe 4X08 to 4X13 controllers must be connected to a voltage between 200 ...240V~ to sup
Automation13-1548XX/49XXSHB039913.5 Networking accessoriesThe modules listed in the following are for controller networking.13.5.1 Connection elements
Automation13-1648XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--K00408858ManualPart KSelection aidApplication examplesDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Selection aid14-148XX/49XXSHB039914 Selection aid14.1 Assignment of controller and motorLenze does not only offer controllers but also a complete moto
Technical Data3-148XX/49XXSHB03993 Technical data3.1 FeaturesController and system features( Control electronics and system software are the same for
Selection aid14-248XX/49XXSHB0399Stop!The peak values of the mains voltage are also reached with low armature voltages(speed ).3. Rated armature curre
Selection aid14-348XX/49XXSHB039914.1.2 Armature chokeWhen using Lenze 48XX/49XX controller adapted to the DC motor, it is notnecessary to use an arma
Selection aid14-448XX/49XXSHB0399The following table indicates planning recommendations for componentscompleting your drive.Requirement/applicationRes
Selection aid15-148XX/49XXSHB039915 Application examplesThe following specifications, processes, and circuitry described are for guidanceonly and must
Selection aid15-248XX/49XXSHB039915.1 Speed control with armature-voltage feedback4900Str099Z1K1F '1 ...F '3LKF ''1 ...F '&ap
Selection aid15-348XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateC083 xxx A Rated field currentC084 xxx ms Ar
Selection aid15-448XX/49XXSHB039915.2 Speed control with resolver4900Str100Z1K1F '1 ...F '3LKF ''1 ...F ''3Q1L1L2L3PEL1
Selection aid15-548XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateC083 xxx A Rated field currentC084 xxx ms Ar
Selection aid15-648XX/49XXSHB039915.3 Torque control with speed limitation4900Str101Z1K1F '1 ...F '3LKF ''1 ...F ''3Q1L1
Selection aid15-748XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateC083 xxx A Rated field currentC084 xxx ms Ar
Contentsi48XX/49XXSHB00399Part A1 Preface and general information 1-1...1.1 About these Operating Instructions ... 1-1...
Technical Data3-248XX/49XXSHB0399Speed feedback systems( Resolver feedback with encoder emulation for superimposed systems(synchronizing systems, posi
Selection aid15-848XX/49XXSHB039915.4 Current-ratio control4900Str102Z1K1F'1...F'3LKF ''1 ...F ''3Q1L1L2L3PEL1 L2 L3L&ap
Selection aid15-948XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateMaster and slaveC083 xxx A Rated field curre
Selection aid15-1048XX/49XXSHB039915.5 Dancer-position control at an unwinder4900Str103L1 L2 L3PEI K BF'4MIK ABM121 28 39 40 59 90 FE8 97X1 X2 X3
Selection aid15-1148XX/49XXSHB03994900Str104+21E401±1C041 CW /CW21 22C012 TC013 Tirif8-1 0 V ... + 1 0 V+nsetC 046C 011C 145/C 146C 025/C 026C 145/
Selection aid15-1248XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateC083 xxx A Rated field currentC084 xxx ms A
Selection aid15-1348XX/49XXSHB039915.6 Hoists4900Str105PEL1 L2 L3PEI K BF'4MIK ABM121 28 39 41 59 90 FE8 9X1 X2 X3 X44900AcwR22ccwA5K3X7PEE5E444
Selection aid15-1448XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateC083 xxx A Rated field currentC084 xxx ms A
Selection aid15-1548XX/49XXSHB039915.7 Speed-ratio synchronism4900Str106MRi = 19.4v = 80 m /m inv = 50 m /m inMRi = 5 .3X5v = 110 m /m inMRi = 5 .3X
Selection aid15-1648XX/49XXSHB0399Parameter settingCode Input DescriptionInput according to motor nameplateMaster and slaveC083 xxx A Rated field curr
Selection aid15-1748XX/49XXSHB0399Code DescriptionInputAdjustment of speed controllerMaster and slaveC011 xxxx rpm Max. max. speedApplication paramete
Technical Data3-348XX/49XXSHB03993.2 General data / application conditionsField ValuesType of protection IP20 to DIN 40050, steel sheet housingPermiss
Selection aid15-1848XX/49XXSHB039915.8 Modular box 221515.8.1 Winding drivePurposeFor winding applications, e.g. winding of a paper reel, the drive ca
Selection aid15-1948XX/49XXSHB0399Compensation of friction, acceleration and breakaway torqueThe friction can be compensated as function or from a tab
Selection aid15-2048XX/49XXSHB0399Digital, freely programmable inputs( Ctrl. inhibit of the automation module( Diameter calculation enable( Initial di
Selection aid15-2148XX/49XXSHB03994900Str108vtL4900Lim it sw itchLim it sw itch R eference sw itchTargetStartvposAcceleration DecelerationFIG 15-10 Dr
Selection aid15-2248XX/49XXSHB0399- Adjustable waiting time- Adjustable number for repetition function- Limited program branching depending on the inp
Selection aid15-2348XX/49XXSHB039915.9 Mains isolation15.9.1 Tipping with mains isolationIn this application proposal, the power stage is connected to
Selection aid15-2448XX/49XXSHB03994900Str109Z1K1F '1 ...F '3LKF ''1 ...F ''3L1 L2 L3L1 L2 L3L'1 L'2 L'3L1
Selection aid15-2548XX/49XXSHB0399Contactor or relay circuit4900Str11020 21 28 39 40 59 90 FEX2 X3 X4490022 A4K3S1S2K2K2 K2.1K1K2.1K4K3K1tdL11L10L20K4
Selection aid15-2648XX/49XXSHB03994900Str11120 21 28 39 40 59 90 FEX2 X3 X44900cw22ccwA4K3S1S2K2K2 K2.1K1K2.1K2K3K1L11L10L20K2Crtl.enableQSPn a c t =
Selection aid15-2748XX/49XXSHB0399Show/Hide Bookmarks
Technical Data3-448XX/49XXSHB03993.3 Rated data3.3.1 Mains voltage 400V( Controllers 4902 to 4907 (4Q controllers)Type 4902 4903 4904 4905 4906 4907Or
Selection aid15-2848XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--L00408859ManualPart LSignal-flow chartsDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Signal-flow charts16-148XX/49XXSHB039916 Signal-flow charts4900Str112-21JOG 1JOG 2JOG xE4 E501±1C041CW /CCW21 22QSPExExC134QSPC012 TC013 TirifC190E301
Signal-flow charts16-248XX/49XXSHB03994900Str113-±1C04121 22C105cw /ccwC 050+C 051nact62636263C 027 C 028C025/C026Enc.const.D ig_In_1X7QSPC 070 VC 071
Signal-flow charts16-348XX/49XXSHB03994900Str114-±1C04121 22C105CW /CCWC 050+C 051nactX7QSPC 070 VC 071 TC 072 KpnnndnC 056C 063C 022, C 023IC 042QSPX
Signal-flow charts16-448XX/49XXSHB03994900Str115a+346-1 0 V ... + 1 0 V+8-1 0 V ... + 1 0 V+C 145/C 005C 025/C 026O ffs e tO ffs e tC 145/C 005C
Signal-flow charts16-548XX/49XXSHB03994900Str115b-+-100 %C047JOG 1JOG 2JOG x01±121 22QSPC 134QSPC 012 TC 013 TirifC 19001C 105QSPnnC 046C 011C146/C147
Signal-flow charts16-648XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--M00408860ManualPart MGlossaryTable of keywordsDC speed controller4800/4900Show/Hide Bookmarks
Technical Data3-548XX/49XXSHB0399( Controllers 4808 to 4813 (2Q controllers)Type 4808 4809 4811 4812 4813Order No. EVD 4808-E EVD 4809-E EVD 4811-E EV
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Glossary17-148XX/49XXSHB039917 GlossaryTerm MeaningAIF Automation interface (X1)CE Communauté Européenne (English: European Community)Code For entry a
Glossary17-248XX/49XXSHB0399Show/Hide Bookmarks
Index18-348XX/49XXSHB039918 Table of keywords0 ... 92Q operation, Change of the direction ofrotation, 4-234Q/2Q operation, 7-60AA/D conversion, 7-29Ab
Index18-448XX/49XXSHB0399Grounding, 4-32Installation, 4-29IT mains, 4- 4Screening, 4-31Signal cables, 4-31Cleaning, 9-1CodeChange, 7-113Code table, 7-
Index18-548XX/49XXSHB0399FAI, 7-29FaultCause, 8- 4History buffer, 8-3Remedy, 8- 4Reset, 12- 1Fault indicationDisplay priority, 7-98Reset, 8-6Fault mes
Index18-648XX/49XXSHB0399Field controller circuit, 7-15, 7-16, 7-17Speed, 7-94InstallationCE-typical drive system, 4-29Connection, 4-5Electrical, 4-2I
Index18-748XX/49XXSHB0399Parameter setting, 7-33Monitoring functions, 7-96Change, 7-96Display priority, 7-98I(2)xt monitoring, 7-101Ixt monitoring, 7-
Index18-848XX/49XXSHB0399Power connection, Standard controller,4-6Power derating, 3-1Process controller, 7-67Inputs, 7- 68Outputs, 7-69Process data ch
Index18-948XX/49XXSHB0399SignalsAnalog connection, 4-14Connection of digital, 4-17Single drives, 4-4Slave, 7-42Digital frequency bar, 7- 42Digital fre
Technical Data3-648XX/49XXSHB03993.3.2 Mains voltage 500V (Variant V014)( Controllers 4903 to 4907 (4Q controllers)Type 4903 4904 4905 4906 4907Order
Index18-1048XX/49XXSHB0399TerminalsChanging the signal assignment, 5-8Control connections, 4-13Type of operation, 7-116TorqueControlled operation, 7-3
Index18-1148XX/49XXSHB0399Show/Hide Bookmarks
Index18-1248XX/49XXSHB0399Show/Hide Bookmarks
Technical Data3-748XX/49XXSHB0399( Controllers 4808 to 4813 (4Q controllers)Type 4808 4809 4811 4812 4813Order No.EVD4808-E-V014EVD4809-E-V014EVD4811-
Technical Data3-848XX/49XXSHB03993.4 Dimensions3.4.1 Controller 4902 to 4X09X1 X2X3 X4 X5 X6 X7X8 X9X10 X11 V1 V2gacbdge”A”4900fikh”A”4900Str001FIG 4
Technical Data3-948XX/49XXSHB03993.4.2 Controllers 4811 to 4813, 4911 to 49134900edbcagmnh4900Str002FIG 4-2 Dimensions of the controllers 4X11 to 4X1
Technical Data3-1048XX/49XXSHB0399Show/Hide Bookmarks
Installation4-148XX/49XXSHB03994 Installation4.1 Mechanical installation4.1.1 Important notes( Ensure free installation space above and below the cont
Contentsii48XX/49XXSHB003994.3 Connection 4-5...4.3.1 Power connection of standard controller 4-6...
Installation4-248XX/49XXSHB03994.2 Electrical installationFor information on the installation according to EMC, see chapter 4.44.2.1 Protection of per
Installation4-348XX/49XXSHB03994.2.2 Protection of the controllerStop!The controllers contain electrostatically sensitive components:Prior to assembly
Installation4-448XX/49XXSHB03994.2.4 Earthing of the control electronicsSingle drives( With factory setting, the reference potential GND of the contro
Installation4-548XX/49XXSHB03994.3 ConnectionConnection between controller and motorLenze controller Motor (to DIN 42017/VDE 0530 part 8)Function Ter
Installation4-648XX/49XXSHB03994.3.1 Power connection of standard controllerZ1K1F’1...F’3LKF’’1...F’’3L1 L2 L3L1 L2 L3L’1L’2L’3L1 L2 L3PE BF’4MM1AIKAB
Installation4-748XX/49XXSHB03994900Str128Z1K1F '1 ...F '3LKF ''1 ...F ''3L1 L2 L3L1 L2 L3L'1 L'2 L'3L1 L2
Installation4-848XX/49XXSHB03994900Str129Z1K1LKF ''1 ...F ''3L1 L2 L3L1 L2 L3L'1 L'2 L'3L1 L2 L3PE BMM1AIKABS1 S2JI
Installation4-948XX/49XXSHB03994.3.2 Separate supply of the field-current bridge at a high motorfield voltageStop!Ensure correct phase connection of t
Installation4-1048XX/49XXSHB0399Z1K1F’1...F’3LKF’’1...F’’3L1 L2 L3L1 L2 L3L’1L’2L’3L1 L2 L3PE BF’4MM1AIKAB S1 S2JIK L1.2 L2.2 L3.2PEL3.1L1.1FF16A500V4
Installation4-1148XX/49XXSHB03994.3.3 Separate supply for the control electronicsStop!Ensure correct phase connection of the separate mains supply.Inc
Contentsiii48XX/49XXSHB00399Part D7 Configuration 7-1...7.1 Speed-controlled operation 7-1...
Installation4-1248XX/49XXSHB03994900Str130Z1Q1F '1 ...F '3LKF ''1 ...F ''3L1 L2 L3L1 L2 L3L'1 L'2 L'3L1 L
Installation4-1348XX/49XXSHB03994.3.4 Control connections15961596159615961596X9X6 X7X8X5X4X2X3X118915X1118915X10V1 V21234567891040 41 44 45K11K14A1 A2
Installation4-1448XX/49XXSHB03994.3.4.1 Connection of analog signals234165 78 109 61 62 63601234789+-X4168 kGNDX1IUIUS2 S1+-+--+8x 3,3nF168 k47 kGND16
Installation4-1548XX/49XXSHB0399Analog inputsTer minal Switch position Use Level Resolution1, 22S3ONOFFSetpoint 2with ground reference (factorysetting
Installation4-1648XX/49XXSHB0399Analog outputs (monitor outputs)Ter minal Switch position Use Level Resolution60 Internal ground, GND61 Actual current
Installation4-1748XX/49XXSHB03994.3.4.2 Connection of digital signals( All digital inputs and outputs are PLC compatible and separated from therest of
Installation4-1848XX/49XXSHB039921 22 2820 E2E1 E3 E4 39E5 41 44 4540 A2A1 A3A4 59A51 2 34 5 67 8910111213-+QSPX3 X43k3k3k3k3k3k3k3k50 mA50 mA50 mA50
Installation4-1948XX/49XXSHB0399Digital inputsName Ter minal Use(factory setting)Level for activation Programmingsee chapter20 Voltage supply 15V, 100
Installation4-2048XX/49XXSHB0399Relay outputTer minal Use(factory setting)4900Str063K11, K14 Floating relay output, contact load capacitiy: 50V / 0.5A
Installation4-2148XX/49XXSHB03994.3.5 Feedback systemsSeveral feedback systems can be connected to the controller and configured:( Armature voltage co
Contentsiv48XX/49XXSHB003997.5.5 Absolute value generator 7-71...7.5.6 Limitation elements 7-72...
Installation4-2248XX/49XXSHB0399The resolver signal or encoder signal can be output for following drives at the digitalfrequency output X8.( Connectio
Installation4-2348XX/49XXSHB0399Pin assignment of socket X5/X9:Pin 1 2 3 4 5 6 7 8 9Signal BAA VE9 GNDZZ LCBPin 8, LC ( ¥)- For encoders without lamp
Installation4-2448XX/49XXSHB03994.3.7 Digital frequency selection and encoder emulationDigital frequency input( Possible digital frequency signals:- I
Installation4-2548XX/49XXSHB0399Digital frequency output / encoder emulationThe output signal of the Sub-D socket X8 can be used for superimposed cont
Installation4-2648XX/49XXSHB03994.3.8 Serial interface RS232/485Danger!The interface RS232C/RS485 is not isolated, i.e. an additional electrical isola
Installation4-2748XX/49XXSHB03994.3.9 Fieldbus connectionNote!Special features of the controller variants V011 and V013:1. The interface module 2110IB
Installation4-2848XX/49XXSHB0399( Variant V013 with PROFIBUS interface moduleThe interface module type 2130IB connects Lenze controllers to the fast s
Installation4-2948XX/49XXSHB03994.4 Installation of a CE-typical drive system4.4.1 General notes( The electromagnetic compatibility of a machine depen
Installation4-3048XX/49XXSHB03994.4.2 Components of the CE-typical drive systemSystem component SpecificationController 4800/4900 DC controllersRFI fi
Installation4-3148XX/49XXSHB0399Signal cables( Always screen digital and analog signal cables.- Always connect the signal cables over the shortest pos
Contentsv48XX/49XXSHB00399Part E8 Troubleshooting and fault elimination 8-1...8.1 Troubleshooting 8-1...
Installation4-3248XX/49XXSHB0399Grounding( Ensure a good equipotential bonding of all system parts (controller, RFI filter,mains choke, etc.) by cable
Installation4-3348XX/49XXSHB03994900Str021LPE410813795112PEPE I K A B6FIG 4-23 Part of the CE-typical drive system with 4902 ... 4907 on a mounting pl
Installation4-3448XX/49XXSHB03994900Str022llL1L2L3PE2 31011981211413L7546FIG 4-24 Part of the CE-typical drive system with 4X08/4X09 on a mounting pla
Installation4-3548XX/49XXSHB03994900Str023llLL1L2L3PE2 3678910111215134FIG 4-25 Part of the CE-typical drive system with 4X11 ... 4X13 on a mounting p
Installation4-3648XX/49XXSHB0399Show/Hide Bookmarks
EDS4900U--C00408852ManualPart CCommissioningDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Commissioning5-148XX/49XXSHB03995 Commissioning5.1 Initial switch-onStop!Prior to initial switch-on of the controller, check the wiring for completene
Commissioning5-248XX/49XXSHB0399Wiring recommendation for speed control with tachoZ1K1F’1...F’3LKF’’1...F’’3Q1L1L2L3PEL1 L2 L3L’1L’2L’3L1 L2 L3PEI K 2
Commissioning5-348XX/49XXSHB0399The following table describes briefly how to commission a DC shunt motor with anattached tacho according to the exampl
Contentsvi48XX/49XXSHB00399Part H12 Automation 12-1...12.1 LECOM1 interface 12-1...
Commissioning5-448XX/49XXSHB03995.2 Input of the motor dataNoteFor internal calculations with field-weakening control, the exact input of thefollowing
Commissioning5-548XX/49XXSHB03995.3 Controller enableFor controller enable, the following conditions must be fulfilled:( Controller enable via termina
Commissioning5-648XX/49XXSHB03995.4 Selection of direction of rotation and quick stopDirection of rotationThe polarity of the output voltage VAand thu
Commissioning5-748XX/49XXSHB0399With the configurations C005 = -X2- or -X3- and activated angle controller(C254 > 0), the drive will be decelerated
Commissioning5-848XX/49XXSHB03995.5 Changing the internal control structureThe internal control structure is adapted to the control task (e. g. speed
Commissioning5-948XX/49XXSHB0399Freely assignable digital outputsThe controller provides 12 freely assignable digital outputs and a relay output.Thefr
Commissioning5-1048XX/49XXSHB0399Freely assignable analog monitor outputsVia the monitor outputs X4/62, X4/63 und X8, internal signals can be output a
Commissioning5-1148XX/49XXSHB0399Show/Hide Bookmarks
Commissioning5-1248XX/49XXSHB0399Show/Hide Bookmarks
During operation6-148XX/49XXSHB03996 During operationThis chapter is part of the Lenze documentation structure.It remains free for the 48XX/49XX DC sp
Contentsvii48XX/49XXSHB00399Part K14 Selection aid 14-1...14.1 Assignment of controller and motor 14-1...
EDS4900U--D00408853ManualPart DConfigurationCode tableDC speed controller4800/4900Show/Hide Bookmarks
The features, data and versions indicated in this Manual met the state of the art atthetimeofprinting.(Printing date: inner cover pages of the parts).
Configuration7-148XX/49XXSHB03997 Configuration7.1 Speed controlled operationFor standard applications, the drive can be immediately commissioned with
Configuration7-248XX/49XXSHB03997.1.1.1 Main set-valueThe speed is determing via via the set-valueset(C046)and related to the adjustablevalue nmax(C01
Configuration7-348XX/49XXSHB0399Code NamePossible settingsCodeNameLenze Selection InfoC038¤ Inputpreselection:JOGset-value1 -1- Selection JOG1-2- Sele
Configuration7-448XX/49XXSHB0399JOG set-value enabling with control via keypad or LECOM interfaceActive the JOG set-values under C045.Code NamePossibl
Configuration7-548XX/49XXSHB0399952110 kW(lin.)S3/2+10 VRef.V = +10 ... 0 VIsetmin max4900Str029FIG 7-2 Connection diagram for external torque reducti
Configuration7-648XX/49XXSHB03997.1.1.6 Acceleration and deceleration times Tir,TifEach acceleration or deceleration time refers to a speed change fro
Configuration7-748XX/49XXSHB0399Code NamePossible settingsLenze Selection InfoC100*¤ Input:Additionalacceleration/decelerationtimes formainset-value-1
Configuration7-848XX/49XXSHB0399Enable of additional acceleration and deceleration timesWith terminal control, the inputs must be assigned according t