Lenze 3200 C Bedienungsanleitung Seite 22

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 38
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 21
Technical data
General data and operating conditions
4
22
Lenze ¯ BA_3241C ¯ 4.0
4 Technical data
4.1 General data and operating conditions
General data
Conformity and approval
Conformity
CE 2004/108/EC EMC Directive
EAC TP TC 020/2011
(TR CU 020/2011)
Electromagnetic
compatibility of technical
means
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Approval
UL UL 508
CSA C22.2
Process Control Equipment (File−No. E236341)
Other
RoHS 2011/65/EU Products are lead−free acc. to directive.
Protection of persons and device protection
Enclosure IP20
Electrical isolation
To the fieldbus Depending on the used MC card
To the process level None
Insulation resistance IEC 61131−2
Protective measures Against short circuit
EMC
Interference emission EN 61000−6−4 Class A (industrial premises)
Noise immunity EN 61000−6−2
Industrial premises
EN 61000−4−2 ESD; severity 3, i.e.
Air discharge: 8 kV,
4 kV with contact discharge
EN 61000−4−3 RF interference (housing)
80 MHz  1000 MHz, 10 V/m 80 % AM
(1 kHz)
EN 61000−4−4 Burst, severity level 3
EN 61000−4−5 Surge, severity 1
EN 61000−4−6 RF cable−guided
150 kHz  80 MHz, 10 V/m 80 % AM
(1 kHz)
Seitenansicht 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 37 38

Kommentare zu diesen Handbüchern

Keine Kommentare