Configuration
8200SHB01997-38
7.5.10.1 Reset integral component and influence
Function The following functions are possible:
Reset the integral component K
I
of the PID controller via terminal.
Set the influence of the PID controller to 0.
Activation C007 = -28- ... -34-, -48-, -50-, -51-:
HIGHlevelatterminalE2
- Reset of K
I
C007 = -48-, -49-, -50-:
HIGHlevelatterminalE4
- Reset influence
The signallevelsare indicatedfor C114 = -0- (see chapter 7.5.14.1)
7.5.10.2 Setpoint selection for the process controller
Code Name Possible settings IMPORTANT
Lenze Choice Info
C181* Setpoint PID
controller
0.00 -480.00 {0.02 Hz} 480.00
Function Selection of a frequency setpoint, e.g. for
the dancer position for a dancer control in a line drive,
the pressure setpoint in a pressure control.
Adjustment C181 = 0
The setpoint of the PID controller is
- selectedexternally(terminal 8 or E1),
- set via the keys (▲, ▼)of the operating module 8201BB.
C181 0
Setpoint selection for the PID controller via this code.
Important
The setpoint selection via this code is only active, if C181 0.
C181 is only stored in parameter set 1.
Special features
The setpoint canalsobe entered asapplicationdatum(C500, C501)(see chapter7.6.3).