14 Parameter reference
14.2 Parameters of the communication module for slot MXI1
98
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13882
C13885
Parameter | Name:
C13881 | Monitoring time: Data exchange
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the "Data Exchange" state is exited, the response parameterised under C13880/1 is carried out when the
monitoring time for data exchange set here has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time ( C13882/1
).
Permanent interruption of PROFIBUS communication
( 78)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13882 | Monitoring time: Watchdog
Data type: UNSIGNED_32
Index: 10693
d
= 29C5
h
Display of the watchdog monitoring time determined by the PROFIBUS master
• A change in the watchdog monitoring time is immediately effective.
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
Permanent interruption of PROFIBUS communication
( 78)
Display area (min. value | unit | max. value)
0 ms 4294967295
Subcodes Info
C13882/1 Watchdog monitoring time
C13882/2 DP-V1 MSC2
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
Selection of the process data which the controller will process in the event of a PROFIBUS failure in order to maintain
internal communication.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value '0'
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT