Seitenansicht 82
Electrical installation
Drive system on the mains
Electrical isolation
4
83
EDKCSDE040 DE/EN/FR 4.0
4.2 Drive system on the mains
This information applies to the ECS drive system, consisting of:
ƒ ECSxE... power supply module
ƒ ECSxK series capacitor module (optional)
ƒ ECSxS/P/M/A series axis module
ƒ Motor
ƒ Accessories
ƒ Wiring
4.2.1 Electrical isolation
The integrated electrical isolation between the power section and the control
section is a protective separation (reinforced insulation) acc. to EN 61800−5−1.
To maintain this protective separation, it must be ensured that the external
24 V supply and all components connected to this supply also have a protective
separation (SELV/PELV) acc. to EN 61800−5−1.
24 V supply DC bus
X6/+24, GND X22
Basic
insulation
(50 V)
Dig. input/output
X6/DI1, DI2, D24, DO1
Reinforced
insulation
(300 V)
Thermostat
X6/T1, T2
CAN
X4 Mains
AIF
X21
X1
Fig. 4−1 Electrical isolation