Technical data
General data and operating conditions
4
22
Lenze ¯ BA_p500 ¯ 3.0
4 Technical data
4.1 General data and operating conditions
General data
Conformity and approval
Conformity
CE 2004/108/EC EMC Directive
EAC TP TC 020/2011
(TR CU 020/2011)
Electromagnetic
compatibility of technical
means
Eurasian Conformity
TR CU: Technical Regulation of
Customs Union
Approval
UL UL 508
CSA C22.2
Process Control Equipment (File−No. E236341)
Other
RoHS 2011/65/EU Products are lead−free acc. to directive.
Protection of persons and device protection
Enclosure
Front panel EN 60529 IP65
Rear panel EN 60529 IP20
Electrical isolation
To the fieldbus Depending on the MC card used
To the process level None
Insulation resistance IEC 61131−2
Protective measures Against short circuit
EMC
Interference emission EN 61000−6−4 Class A (industrial premises)
Noise immunity EN 61000−6−2
Industrial premises
EN 61000−4−2 ESD; severity 3, i.e.
Air discharge: 8 kV,
4 kV with contact discharge
EN 61000−4−3 RF interference (housing)
80 MHz  1000 MHz, 10 V/m 80 % AM
(1 kHz)
EN 61000−4−4 Burst, severity level 3
EN 61000−4−5 Surge, severity 1
EN 61000−4−6 RF cable−guided
150 kHz  80 MHz, 10 V/m 80 % AM
(1 kHz)
Operating conditions
Ambient conditions
Climatic
Storage/transport EN 60721−3−2 2K3:
−25 ... +80 °C depending on the air humidity
(see diagrams 23)
Operation EN 60721−3−2 3K3:
0 ... +55 °C depending on the air humidity
(see diagrams 23)
Air humidity EN 60721−3−3 3K3 (without condensation, relative humidity 10 ... 95 %)
Pollution EN 61131−2 Degree of pollution 2
Mechanical
Vibration EN 61131−2 1 g
Shock EN 61131−2 15 g
Site altitude
Storage/transport < 12000 m amsl
Operation < 3000 m amsl