S94P01B2
14
Installation
NOTE
The ground connection from the filter must be wired to solid earth
ground, not machine ground.
If the end-user is using a CE-approved motor, the AC filter combined with the
recommended motor and encoder cables, is all that is necessary to meet the EMC
directives listed herein. The end user must use the compatible filter to comply with CE
specifications. The OEM may choose to provide alternative filtering that encompasses
the PositionServo 940 drive and other electronics within the same panel. The OEM has
this liberty because CE requirements are for the total system.
3.4 Heat Sinking
The PositionServo 940 drive contains sufficient heat sinking within the specified ambient
operating temperature in their basic configuration. There is no need for additional heat
sinking. However, you must ensure that there is sufficient clearance for proper air
circulation. As a minimum, you must allow an air gap of 25 mm above and below the
drive.
3.5 Line (Mains) Fusing
External line fuses must be installed on all PositionServo drives. Connect the external
line fuse in series with the AC line voltage input. Use fast-acting fuses rated for 250
VAC or 600 VAC (depending on model), and approximately 200% of the maximum
RMS phase current.
3.6 Fuse Recommendations
Type
(1)
AC Line
Input Fuse
(1ø/3ø)
Miniature
Circuit Breaker
(1)
(1ø/3ø)
AC Line
Input Fuse or
Breaker
(2)
(3)
(N. America)
DC Bus Input
Fuse
(4)
Amp Ratings
E94P020S1N M20/M10 C20/C10 20/10 10
E94P040S1N M32/M20 C32/C20 30/20 20
E94P020S2F M20 C20 20 15
E94P040S2F M20 C20 20 20
E94P080S2F M32 C32 32 40
E94P100S2F M40 C40 40 45
E94P020Y2N M20/M16 C20/C16 20/15 15
E94P040Y2N M20/M16 C20/C16 20/15 20
E94P080Y2N M32/M20 C32/C20 30/20 40
E94P100Y2N M40/M25 C40/C25 40/25 45
E94P120Y2N M50/M32 C50/C32 50/30 55
E94P020T4N M10 C10 10 10
E94P040T4N M10 C10 10 20
E94P050T4N M16 C16 15 25
E94P060T4N M20 C20 20 30
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.
(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.
(3) Thermal-magnetic type breakers preferred.
(4) DC-rated fuses, rated for the applied voltage. Examples Bussman KTM or JJN as appropriate.