
6 Commissioning
6.3 Possible DIP switch settings
32
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Setting the station address via the »Engineer«
In the »Engineer«, the station address can be set via the Settings tab.
Invalid addresses are displayed in red in the Station address input field (code C13899
/ C14899).
Save the changed settings via the device command C00002 = 11 (save start parameters).
6.3.2 Establishing EMF2133IB compatibility
Establishing EMF2133IB compatibility is necessary if you need to communicate with systems using
an EMF2133IB PROFIBUS communication module.
Software compatibility can be set via DIP switch 2133.
Switch Switch position Function
2133 ON Establishing EMF2133IB compatibility
OFF No EMF2133IB compatibility
Note!
• In the compatibility mode "EMF2133IB", only the DRIVECOM parameter data channel
(DP-V0) and the Lenze device control can be used.
• Switch off the voltage supply of the communication module and then on again in
order to activate changed settings.
Communication manual for the EMF2133IB module
Here you can find information on the configuration of the EMF2133IB communication
module and the identification of the module on the bus.
Kommentare zu diesen Handbüchern