Commissioning
Configuration with internal DIP switches
Settings in the operating mode (normal operation)
7
l
63
EDBMZ9374X DE/EN/FR 4.2
Setting the CAN bus baud rate
DIP switch Baud rate [kBit/s]
1000 500 250 125 100 50 20 10
9 OFF OFF OFF OFF ON ON ON ON
10 OFF OFF ON ON OFF OFF ON ON
11 OFF ON OFF ON OFF ON OFF ON
ƒ Set the baud rate of the terminal extensions with the DIP switches 9 ... 11.
– The baud rate of the terminal extension must be identical with the baud
rate of the controller (master).
– In the Lenze default setting, the master has the baud rate 500 kBit/s
(C0351 = 0).
) Note!
The baud rate to be set depends on the length of the system bus
cable. (¶ 50, Technical data)