Lenze EPM−H310 Bedienungsanleitung Seite 62

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 102
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 61
Troubleshooting and fault elimination
Fault messages
7
62
EDBPM−H310 DE/EN/FR 7.1
7 Troubleshooting and fault elimination
7.1 Fault messages
Call up the status messages of the operating unit to display the fault message
that occurred last. ( 58)
Display Fault Cause Remedy
NO ERROR No fault
PR ERROR Faulty data
exchange
Connection between operating
unit and PC is faulty
l Check that the connections are
firmly seated.
l Check cable for damages
COM BROK Communication
interrupted
Serial data cable between
operating unit and PC is
defective or not correctly
connected
l Check Sub−D connector for correct
connection and firm seating.
l Replace serial data cable
ASIC ko1 Communication
with system
bus (CAN)
interrupted
l Faulty wiring (e. g. polarity)
of the system bus
l Faulty parameterisation of
interface (baud rate,
address, identifier)
l Check wiring of system bus (CAN)
(
52)
l Check parameter setting ( HMI
Designer − Getting started).
ASIC ko2
ASIC ko3
ASIC ko4
RESET
SDOERR 6
SDOERR 5
SDOERR 3
Seitenansicht 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 101 102

Kommentare zu diesen Handbüchern

Keine Kommentare