Function block library LenzeElectricalShaft.lib
Special functions
2.1.4 Homing function (L_REF)
2−23
L
LenzeElectricalShaft.lib EN 1.2
Homing with TouchProbe (TP) or zero−pulse (MP)
The reference point is at the next TouchProbe signal, or zero−pulse plus the reference point offset.
· Mode 8 ( byHomingMode = 8):
Move to the home position in CW rotation.
Home position offset dnRefOffset is entered as positive.
· Mode 9 ( byHomingMode = 9):
Move to the home position in CCW rotation.
Enter the reference point offset dnRefOffset or zero−pulse as a negative value.
Take care that the TP has been parameterized in the system block!
Example: Mode 8 with a 9300 Servo PLC through MCTRL_MotorControl
Abb. 2−17 Example: Mode 8 with a 9300 Servo PLC through MCTRL_MotorControl
Settings
· In Parameter Manager: byHomingMode = 8
· C0911=0, homing to zero−pulse or
C0911=1, homing to TouchProbe (terminal X5/E4).
· With C0911=1, C0912 can be used to select whether a rising or falling edge will trigger a
TouchProbe.
(C0912 = 0: rising edge; C0912 = 1: falling edge)
· With C0910 a delay can be set for a TP/MP.