Lenze Drive Server Bus server S7 getting started Bedienungsanleitung Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 63
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
Busserv er S7
L
82 Busserver S7 DE/EN 1.0
Tip!
Proceed as follows to identify the sub-network ID in the STEP 7 program:
1. Start the ”NetPro” service program, e. g. by double-clicking a network in the SIMATIC manager
or clicking ”Connections” when the CPU is focussed.
2. Ri ght-click the network connecting the controls with each other and select the Object
Properties command from the context menu.
3. Enter the sub-network ID indic ated in the Object Properties dialog box in the Lenze S7
configuration tool.
The below figure shows an example of a possible configuration:
Tip!
If controllers are connected to the PROFIBUS of the master PLC and the PROFIBUS of the sub-system,
two PLCs must be configured in the Lenze S7 configuration tool.
In this case, the master PLC data are identical for both configuration entries.
For the sub-system PLC, you also have to enter the sub-system data as described above.
Show/Hide Bookmarks
Seitenansicht 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 62 63

Kommentare zu diesen Handbüchern

Keine Kommentare