Electrical installation
Ethernet POWERLINK connection
6
EDK94AYCEP DE/EN/FR/ES/IT 4.0
39
H2_EthernetAnschluss−Ethernet_KabelSpezifikation
Ethernet POWERLINK connection
You can use a standard Ethernet patch cable for connection to the communication module
(see "Ethernet cable specifications" (41)).
Mounting and dismounting of the Ethernet cables has been optimised for the use of
connectors according to the "Automation Initiative of German Domestic Automobile
Manufacturers" (AIDA).
Note!
Plug/remove the Ethernet cable plug vertically into/from the socket to make
sure that the RJ45 socket will not be damaged.
ƒ The Ethernet POWERLINK connection is made via RJ45 sockets X211 and X212.
ƒ Do not wire, if possible, more than 10 nodes in succession in a network line.
ƒ In case of more than 10 nodes you should deactivate the automatic calculation of the
hub level in the »Engineer« and enter it manually to increase the performance.
ƒ At a cycle time of 1 ms, approx. 25 mandatory nodes can be operated.
– The number of nodes can be increased if the EPL cycle time is increased as well.