Commissioning
Before switching on
7
EDK94AYCEP DE/EN/FR/ES/IT 4.0
43
H1inbet−Teilnehmeradresse_E94AYCEP
7 Commissioning
Before switching on
Stop!
Before switching on the standard device with the communication module for
the first time, check the entire wiring for completeness, short circuit and earth
fault.
Setting the node address
E94YCEP001D
ƒ In case of several interconnected Ethernet POWERLINK nodes, the addresses must
differ from each other.
ƒ For each device, the node address at the DIP switches 1 ... 128 and in code C13044 /
C14044must be set identically.
ƒ Valid node address in the Ethernet POWERLINK network:
Node address Meaning
240 E94AYCEP is a managing node.
1  100 E94AYCEP is a controlled node with another E94AYCEP as managing node.
1  239 E94AYCEP is a controlled node with a managing node of a different
manufacturer.
ƒ Lenze setting of the DIP switches 1 ... 128 = OFF (invalid value "0")
ƒ The housing labelling corresponds to the valencies of the individual DIP switches for
determining the station address.