9 Parameter data transfer
9.3 Supported PMS services
42
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.4 Read/Write
The "Read" PMS service reads parameters from the inverter. The inverter outputs the requested
parameter or an error message.
The "Write" PMS service writes on parameters of the inverter. The inverter outputs a positive
feedback or an error message.
The following error messages can occur:
9.3.5 Get-OD
The "Get-OD" PMS service reads out the object description for every parameter and data type.
Error Class Error code Additional
Code
[hex]
Description
6 3 0x00 No access authorisation
6 5 0x10 Impermissible job parameter
650x11Invalid subindex
6 5 0x12 Data length too large
6 5 0x13 Data length too small
6 6 0x00 Object is no parameter
6 7 0x00 Object does not exist
6 8 0x00 Data types do not comply with each other
8 0 0x00 Request cannot be executed
8 0 0x20 Request cannot be executed at the moment
8 0 0x21 Cannot be executed because of local control
8 0 0x22 Cannot be executed because of device state
8 0 0x30 Quit value range / parameter can only be changed when the
controller is inhibited.
8 0 0x31 Parameter value too high
8 0 0x32 Parameter value too low
8 0 0x33 Sub parameter outside the value range
8 0 0x34 Value of the subparameter is too high
8 0 0x35 Value of the subparameter is too low
8 0 0x36 Maximum value is lower than minimum value
8 0 0x41 Communication object cannot be displayed on process data
8 0 0x42 Length of the process data exceeded
8 0 0x43 General collision with other values
Seitenansicht 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 77 78

Kommentare zu diesen Handbüchern

Keine Kommentare