30P94MOD01C
Reference
NOTE:
In true Modbus, 3X and 4X Registers are numbered starting at 1. This is known as ‘one based’ addressing.
However, when transmitted to a slave over the serial link, the actual address transmitted is one less.
Some Modbus masters will allow for the first register number to be 0. This is known as ‘zero based’
addressing. If this is the case, the Modbus register numbers listed in this manual must be offset by -1 to
properly program a master using ‘zero-based’ addressing.
Index
Name
Type
Format
EPM
Access
Description Range Unit RAM
Registers
32bit
Integer
Access
4X
Register #
RAM
Register
32bit
Float
Access
4X
Register #
EPM
Reg Copy
32bit
Integer
Access
4X
Register #
EPM
Reg Copy
32bit
Float
Access
4X
Register #
RAM
Register
16bit
Signed
Integer
4X
Register #
EPM
INT16
4X
Register #
1 VAR_IDSTRING N R Drive’s identification string 3 515 1027 1539 2050 2306
2 VAR_NAME Y R/W Drive’s symbolic name 5 517 1029 1541 2051 2307
3 VAR_SERIAL_NUMBER R Drive’s serial number 7 519 1031 1543 2052 2308
4 VAR_MEM_INDEX R/W Position in RAM file (0 - 32767) 9 521 1033 1545 2053 2309
5 VAR_MEM_VALUE R/W Value to be read or written to the RAM file 11 523 1035 1547 2054 2310
6 VAR_MEM_INDEX_
INCREMENT
R/W Holds value the MEM_INDEX will modify once
the R/W operation is complete
13 525 1037 1549 2055 2311
7 VAR_VELOCITY_ACTUAL R Actual measured motor velocity
NOTE: Only applicable to MVOB drives with
Firmware 4.00 and higher.
15 527 1039 1551 2056 2312
8 VAR_RSVD_2 17 529 1041 1553 2057 2313
9 VAR_DFAULT R Drive Default Settings 19 531 1043 1555 2058 2314
10 VAR_M_ID mtr Y R/W* Motor ID 21 533 1045 1557 2059 2315
11 VAR_M_MODEL mtr Y R/W* Motor model 23 535 1047 1559 2060 2316
12 VAR_M_VENDOR mtr Y R/W* Motor vendor 25 537 1049 1561 2061 2317
13 VAR_M_ESET mtr Y R/W* Motor Feedback Resolver: ‘Positive for CW’
0 - none
1 - Positive for CW
0 - 1 27 539 1051 1563 2062 2318
14 VAR_M_HALLCODE mtr Y R/W* Hallcode index 0 - 5 29 541 1053 1565 2063 2319
15 VAR_M_HOFFSET mtr Y R/W* Reserved 31 543 1055 1567 2064 2320
16 VAR_M_ZOFFSET mtr Y R/W* Resolver Offset 0 - 360 33 545 1057 1569 2065 2321
17 VAR_M_ICTRL mtr Y R/W* Reserved 35 547 1059 1571 2066 2322
18 VAR_M_JM mtr Y R/W* Motor moment of inertia Jm 0 - 0.1 Kgm2 37 549 1061 1573 2067 2323
19 VAR_M_KE mtr Y R/W* Motor voltage or back EMF constant Ke 1 - 500 V/Krpm 39 551 1063 1575 2068 2324
20 VAR_M_KT mtr Y R/W* Motor torque or force constant Kt 0.01 - 10 Nm/A 41 553 1065 1577 2069 2325
21 VAR_M_LS mtr Y R/W* Motor phase-to-phase inductance Lm 0.1 - 500 mH 43 555 1067 1579 2070 2326
22 VAR_M_RS mtr Y R/W* Motor phase-to-phase resistance Rm 0.01 - 500 [Ohm] 45 557 1069 1581 2071 2327
23 VAR_M_MAXCURRENT mtr Y R/W* Motor’s max current(RMS) 0.5 - 50 [A]mp 47 559 1071 1583 2072 2328
24 VAR_M_MAXVELOCITY mtr Y R/W* Motor’s max velocity 500 - 20000 RPM 49 561 1073 1585 2073 2329
25 VAR_M_NPOLES mtr Y R/W* Motor’s poles number 2 - 200 51 563 1075 1587 2074 2330
26 VAR_M_ENCODER mtr Y R/W* Encoder resolution 256 - 65536
* 12/Npoles
PPR 53 565 1077 1589 2075 2331
27 VAR_M_TERMVOLTAGE mtr Y R/W* Nominal Motor’s terminal voltage 50 - 800 [V]olt 55 567 1079 1591 2076 2332
28 VAR_M_FEEDBACK mtr Y R/W* Feedback type
1 - Encoder; 2 - Resolver
1 - 2 57 569 1081 1593 2077 2333
29 VAR_ENABLE_SWITCH_
TYPE
W Y R/W Enable switch function
0 - inhibit only; 1 - Run
0 - 1 Bit 59 571 1083 1595 2078 2334
30 VAR_CURRENTLIMIT F Y R/W Current limit [A]mp 61 573 1085 1597 2079 2335
31 VAR_
PEAKCURRENTLIMIT16
F Y R/W Peak current limit for 16kHz operation [A]mp 63 575 1087 1599 2080 2336
32 VAR_PEAKCURRENTLIMIT F Y R/W Peak current limit for 8kHz operation [A]mp 65 577 1089 1601 2081 2337
33 VAR_PWMFREQUENCY W Y R/W PWM frequency selection
0 - 16kHz; 1 - 8kHz
0 - 1 67 579 1091 1603 2082 2338
* These are all R/W variables but they only become active after variable 247 is set.