Lenze EMB934x Bedienungsanleitung Seite 116

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 206
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 115
Electrical installation
Regenerative power supply module EMB9343
Power connections
5
116
EDBMB9340 DE/EN/FR 12.0
5.4 Regenerative power supply module EMB9343
5.4.1 Power connections
Stop!
Please observe the following operating conditions:
ƒ Regenerative power supply modules must not be connected in parallel in
the DC bus.
ƒ The regenerative power supply module has no overload protection which
means:
– Please observe the permissible mains voltage and maximum currents
( 86). Higher voltages or currents destroy the regenerative power supply
module.
– For protecting the regenerative power supply module against overload
during the regenerative feedback we recommend the use of a brake
chopper. Please observe the circuit proposals ( 124).
ƒ Please observe national and local regulations!
Seitenansicht 115
1 2 ... 111 112 113 114 115 116 117 118 119 120 121 ... 205 206

Kommentare zu diesen Handbüchern

Keine Kommentare