Lenze EMB9352−C Bedienungsanleitung Seite 88

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 174
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 87
Mechanical installation
Important notes
6
88
EDBMB935X DE/EN/FR 13.0
6 Mechanical installation
6.1 Important notes
ƒ Only use the braking units as built−in units!
ƒ Observe mounting clearances!
Observe clearance of 100 mm at the top and at the bottom.
ƒ Make sure that the cooling air can access and the exhaust air can escape
unimpededly.
ƒ If the cooling air is polluted (dust, lints, greases, aggressive gases), which
may affect the function of the braking units:
Take adequate countermeasures, e. g. separate air guide, installation of
filter, regular cleaning, etc.
ƒ Do not exceed the permissible range of the ambient operating
temperature (see chapter 4.1).
ƒ If the braking units are permanently exposed to vibrations or shocks:
Check the use of vibration dampers.
Possible mounting positions
ƒ Vertically on the rear panel of the control cabinet, power connections
facing upwards
Fixed with enclosed fixing rails (see chapter 6.2)
Thermally separated with an external heatsink ("Push−through
technique") (see chapter 6.3)
Thermally separated with an external convection cooler ("Cold plate"
technology) (see chapter 6.4)
Danger!
ƒ In case of fault, brake resistors can reach very high temperatures;
the brake resistor may even burn down, e. g. in the case of
mains overvoltage,
application−specific overload,
internal error.
ƒ Therefore mount the brake resistors so that no damage can be
caused by the possible, very high temperatures.
Seitenansicht 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 173 174

Kommentare zu diesen Handbüchern

Keine Kommentare