Troubleshooting and fault elimination
Troubleshooting
Fault analysis via LECOM status words (C0150/C0155)
4
35
EDKVS93−02 EN 3.0
4.2.3 Fault analysis via LECOM status words (C0150/C0155)
The LECOM status words (C0150/C0155) are coded as follows:
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0150 Status word 0
Device status word for networking
via automation interface (AIF)
Read only
0 {1} 65535 Controller evaluates information as
16 bits (binary−coded)
Bit 0 Not assigned
Bit 1 Pulse inhibit (IMP)
Bit2 Not assigned
Bit3 Not assigned
Bit4 Not assigned
Bit5 Not assigned
Bit 6 n = 0
Bit 7 Controller inhibit (CINH)
Bit 8 Device status bit 1
Bit 9 Device status bit 2
Bit10 Device status bit 3
Bit11 Device status bit 4
Bit12 Warning
Bit13 Message
Bit14 Not assigned
Bit15 Not assigned
C0155 Status word 2 0
Status word 2 (advanced status
word)
Display only
0 {1} 65535 Controller interprets information as
16 bit (binary coded)
Bit 0 Active fault
Bit 1 M
max
reached
Bit 2 I
max
reached
Bit 3 Pulse inhibit(IMP)
Bit 4 Ready for operation (RDY)
Bit 5 Controller inhibit (CINH)
Bit 6 TRIP active
Bit 7 Initialisation
Bit 8 Motor direction of rotation (Cw/CCw)
Bit 9 Not assigned
Bit 10 Not assigned
Bit 11 Not assigned
Bit 12 Not assigned
Bit 13 Not assigned
Bit 14 Not assigned
Bit 15 Not assigned
Kommentare zu diesen Handbüchern