6 Electrical installation
Wiring according to EMC
EDK82ZAFSC DE/EN/FR 5.0
36
H1_E_INST−Hi_EMV
6 Electrical installation
Wiring according to EMC
Please observe the following for wiring according to EMC guidelines:
Note!
ƒ Separate control cables from motor cables.
ƒ Lead the shields as far as possible to the terminals (unshielded core length
< 40 mm).
ƒ Connect control and data cable shields as follows:
Analog signal cable shields must be connected with one end at the
inverter.
Digital signal cable shields must be connected with both ends.
ƒ More information about wiring according to EMC guidelines can be
obtained from the corresponding documentation for the standard device.