Commissioning
DIP switch position
7
EDK82ZAFSC DE/EN/FR 5.0
41
−H2−DIP−Schalter_Tabelle
DIP switch position
1
ON
234
5
ON
OFF
Note!
ƒ Make sure to set the DIP switch and C0034 to the same range, otherwise
the analog input signal at X3/8 will be interpreted incorrectly by the basic
device.
ƒ If a setpoint potentionmeter is supplied internally via X3/9, make sure to
set the DIP switch to the voltage range 0 ... 5 V. Otherwise it will be
impossible to cover the entire speed range.
Signal at X3/8
Switch position
C0034
1 2 3 4 5
0 ... 5V OFF OFF ON OFF OFF 0
0 ... 10 V (Lenze setting) OFF OFF ON OFF ON 0
0 ... 20 mA OFF OFF ON ON OFF 0
4 ... 20 mA OFF OFF ON ON OFF 1
4 ... 20 mA (open−circuit monitored) OFF OFF ON ON OFF 3
−10 ... +10 V ON ON OFF OFF OFF 2