Lenze E94AMHE Bedienungsanleitung Seite 71

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 214
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 70
Wiring the device modules
Communication modules
8
71
EDK94AMH24 DE/EN/FR/ES/IT 3.1
DIP switch
Pos. Description
Addressing of the bus node
Baud
CAN Address
O
N
cdba
64
32
16 8
421
A
9400CAN003
Fig. 8−3 Arrangement and labelling of the DIP switches
For the DIP switches that are placed at the front
ƒ the node address (labelling "1" ... "64") and
ƒ baud rate (labelling "a" ... "d")
can be set.
Note!
If all address switches adopt the "OFF" position when the basic device is
switched on, the configurations of codes C00350 (nodes address) and C00351
(baud rate) apply.
Switch the voltage supply of the basic device off and then on again to activate
altered settings.
Setting the node address
The node address of the drive is calculated from the sum of all address switches in the "ON"
position.
Setting the baud rate
d c b a Baud rate
OFF ON ON OFF 10 kbit/s
OFF ON OFF ON 20 kbit/s
OFF OFF ON ON 50 kbit/s
OFF OFF ON OFF 125 kBit/s
OFF OFF OFF ON 250 kbit/s
OFF OFF OFF OFF 500 kbit/s
ON ON ON OFF 800 kbit/s
OFF ON OFF OFF 1000 kbit/s
OFF ON ON ON Auto baud
Displays
Pos. Colour Condition Description
MS Green On Communication module is supplied with voltage.
DE Red On Communication module is not accepted by the standard device
(see notes given in the documentation for the standard device).
BS Green
Signalling according
to DR303−3
CANopen state ("Z")
BE Red CANopen error ("F")
Seitenansicht 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 213 214