3 Safe configuration
3.6 Safety bus
40
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFIsafe parameter
These PROFIsafe parameters and contents are supported:
[3-10] Supported PROFIsafe parameters
Diagnostic messages
Faulty configurations of the PROFIsafe parameters are reported to the safety PLC with a diagnostic
telegram (communication manual PROFINET).
Diagnostic information
GSDML file
All information on the configuration of the PROFINET system is contained in the GSDML file. Thus,
the integration is easy and user-friendly.
PROFIsafe parameter
Name Description Valid contents
F_Source_Add PROFIsafe source address of the safety PLC 0x01 ... 0xFFFE
F_Dest_Add PROFIsafe target address of the safety system
DIP switch:
Code:
0x01 ... 0x03FF
0x01 ... 0xFFFE
F_WD_Time PROFIsafe monitoring time of the safety system 110 ... 65535 ms
F_Check_SeqNr Check of the sequence no. in CRC
V1 mode:
V2 mode:
0
not relevant
F_Check_iPar Check of the iParameters CRC3 in CRC 0
F_SIL Supported SIL (Safety Integrity Level)
SIL1:
SIL2:
SIL3:
0
1
2
F_CRC_Length Length of CRC
V1-mode/2-byte-CRC:
V2-mode/3-byte-CRC:
1
0
F_Block_ID Identification of the parameter type 0
F_Par_Version Version of the safety layer
V1 mode:
V2 mode:
0
1
F_Par_CRC cyclic CRC is calculated
Error number Description
64 The set PROFIsafe target address does not comply with the F_Dest_Add parameter.
65 The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF
66 The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.
67 The F_WD_Time parameter has the invalid value 0 ms.
68 The F_SIL parameter does not have the valid value 0 ... 2.
69 The F_CRC_Length parameter does not have the valid value 1.
70 The version of the PROFIsafe parameter set is wrong.
71 CRC1 error