7 Parameter reference
7.1 Parameter list | C15003
52
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15003
C15010
C15011
C15012
Parameter | Name:
C15003 | Command status
Data type: UNSIGNED_16
Index: 9572
d
= 2564
h
Status of the current command
• The command is repeated in the high byte.
• In the low byte the status is displayed:
0x00: No command
0x01: Command executed
0x02: Password invalid
0x03: Command in process
0x04: Command not known
0x05: Command error
Display range (min. value | unit | max. value)
0 2309
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15010 | Parameter set status
Data type: UNSIGNED_8
Index: 9565
d
= 255D
h
Selection list (read only)
0 No parameter set
1 Valid parameter set
2 Read error - memory module
3 Unequal parameter set
4 CRC error
5 Version error
6 Format error
7 Plausibility error
8 Assignment error
9 Local read error
10 Communication error standard
device
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15011 | Parameter CRC
Data type: UNSIGNED_32
Index: 9564
d
= 255C
h
Parameter checksum (CRC = Cyclic Redundancy Code)
Display range (min. value | unit | max. value)
0 4294967295
Subcodes Information
C15011/1 CRC safety system
C15011/2 CRC memory module
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15012 | Password
Data type: UNSIGNED_32
Index: 9563
d
= 255B
h
This code is for device-internal use only and must not be written to by the user!