Electrical installation
Wiring of the PROFIBUS
6
EDK94AYCPM DE/EN/FR/ES/IT 6.0
39
H1_E_INST−Steckerleiste_Schraubanschl_15
6 Electrical installation
Wiring of the PROFIBUS
ƒ Wire the PROFIBUS nodes to each other.
Only use cables which correspond to the listed specifications (40).
ƒ Activate the bus terminating resistor in the bus connector at the first and last
physical node.
PROFIBUS cables with an integrated bus terminating resistor can be freely
purchased from various cable manufacturers.
The bus terminator is supplied by the node. The external supply of the
communication module feeds the bus terminator independently of the standard
device supply (43).
Note!
ƒ If you want to disconnect individual bus stations, ensure that the bus
terminators at the first and last physical bus station remain active.
ƒ The bus terminator is no longer active if ...
the connector has been pulled out e.g. in the event of service;
the voltage supply of the communication module has been switched
off.