Installation
Electrical installation
5
2111 INTERBUS fieldbus module
5.4
5.4.3
L
5.4-4
EDSIBS-1.0-06/2003
400 m
400 m
3.1
INTERBUS-Loop 100 m
10 m
82XX
+
2112
8200 vector
+
2111
93XX
+
2111
82XX
+
2111
93XX
+
2112
8200 vector
+
2112
3.1
3.1
3.2
3.23.2
3.2
4.2
4.2 4.24.2
2
4
4.1
4.14.1
1
3
2111IBU001
Fig. 5.4-2 Wiring example, INTERBUS (baud rate 500 kbit/s)
Pos. Element Explanation
1 INTERBUS master with
interface module
The bus system is a master-slave system, i.e. an INTERBUS master is connected
to several field devices (slaves).
2 INTERBUS loop bus
terminal
The bus terminal connects a long distance bus to a peripheral bus.
3 Remote bus
Fig. 5.4-2 Pos. 3
The following connections are possible with remote buses:
the INTERBUS master interface module and first bus terminal or first 2111
fieldbus module.
the bus terminal and t he 2111 fieldbus module
two 2111 fieldbus modules
3.1 Long distance bus module Bus participant in the long distance bus; e.g. Lenze controller with INTERBUS
module (slave). Networking does not require bus terminals.
3.2 Remote bus cable Connects the INTERBUS master interface module with the bus terminal and/or
the long distance bus modules.
4 INTERBUS loop, peripheral
bus
Fig. 5.4-2 Pos. 4
Connection in a peripheral-bus station
A peripheral-bus station consists of:
a bus terminal (Fig. 5.4-2 pos. 2)
up to eight peripheral bus modules (Fig. 5.4-2 pos. 3)
4.1 INTERBUS loop module Bus participant in the INTERBUS loop; e.g. Lenze controller with INTERBUS loop
module 2112
4.2 INTERBUS loop cable Connection within the loop
Features:
Communication medium RS485
Network topology Ring
Maximum number of controllers 62
Baud rate / cable length 500 kbit/s / 400 m
Specification of INTERBUS remote bus cable 5
Cable type Yard goods:
IBS RBC Meter-T, order No. 28 06 28 6 (Fa. Phoenix Contact)
Number of conductors 3 x 2, paired with common shielding
Conductor cross-section >0.2mm
2
DC cable resistance <96/km
Impedance, characteristic 120 Ω±20 % (f = 64 kHz)
100
Ω±15 (f > 1 MHz)
Capacitance per unit length < 60 nF/km (f = 800 Hz)
Wiring example