Drive PLC
System blocks
2.2 AIF1_IO_AutomationInterface (node number 41)
2−5
L
DrivePLC DE 6.0
User data
The received 8 bytes of user data are assigned to several variables of different data types. Data can
therefore be evaluated as —
binary information (1 bit)
control word/quasi−analog value (16 bits)
angle information (32 bits)
in the PLC program.
Byte Variable (1 bit) Variable (16 bits) Variable (32 bits)
1, 2 AIF1_bInB0_b
AIF1_bInB1_b
AIF1_bInB2_b
AIF1_bCtrlQuickstop_b
AIF1_bInB4_b
...
AIF1_bInB7_b
AIF1_bCtrlDisable_b
AIF1_bCtrlCInhibit_b
AIF1_bCtrlTripSet_b
AIF1_bCtrlTripReset_b
AIF1_bInB12_b
...
AIF1_bInB15_b
AIF1_wDctrlCtrl
3, 4
AIF1_nInW1_a
5, 6 AIF1_bInB0_b
...
AIF1_bInB15_b
AIF1_nInW2_a
AIF1_dnInD1_p
7, 8 AIF1_bInB16_b
...
AIF1_bInB31_b
AIF1_nInW3_a
Tip!
Drive PLC:
All variables assigned to byte 1/2 can be freely used in the PLC program.
9300 Servo PLC:
In addition to signals such as IMP and CINH, the SB status word DCTRL contains some freely
assignable signals which can be overwritten via the variables DCTRL_bStateB..._b of the
SB DCTRL. More detailed information about the SB DCTRL can be found in the
"9300 Servo PLC" Online Manual.
The control signals for the quick stop (QSP), DISABLE, CINH, TRIP−SET and TRIP−RESET
function can also be read and processed via the following variables:
AIF1_bCtrlQuickstop_b
AIF1_bCtrlDisable_b
AIF1_bCtrlInhibit_b
AIF1_bCtrlTripSet_b
AIF1_bCtrlTripReset_b
The remaining 11 bits (AIF1_bCtrlB..._b) can be used to control additional functions/function
blocks.