Lenze PC-based Automation Industrial PC Bedienungsanleitung Seite 110

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 226
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 109
Industrial PC | Parameter setting & configuration
Visualisation with »VisiWinNET®«
Constellation and connection
110 L 2.5 EN - 01/2012
13.3.2 Inserting the OPC tunnel in »VisiWinNET®«
The OPC tunnel is the communication channel between »VisiWinNET®« and the OPC
servers of the IPC. You have to integrate the OPC tunnel once into your project.
How to integrate the OPC server into your project:
1. Open the Project explorer.
2. Select the entry New in the context menu of the node VariablesChannels.
Go to the Add channel context menu and select the "OPC server" Channel type.
3. Go to OPC server/driver and press the button and select the OPC tunnel
Lenze.Digitec.OPCTunnel.DA in the OPC server.
4. Click the Browser button.
5. Select the VisiWinNET.LenzeVariables.Brw.dll entry from the selection list.
6. Click the OK button.
The OPC tunnel can be selected in the Project Explorer.
Seitenansicht 109
1 2 ... 105 106 107 108 109 110 111 112 113 114 115 ... 225 226

Kommentare zu diesen Handbüchern

Keine Kommentare