Lenze PC-based Automation Industrial PC Bedienungsanleitung Seite 188

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 226
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 187
Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
188 L 2.5 EN - 01/2012
C1096/29
C1096/30
C1096/31
C1096/32
C1096/33
Parameter | Name:
C1096/29 | ECAT: Forwarded Rx error counter - port 1
Data type: UNSIGNED_8
Index: 23479.29
d
=
0x5BB7.0x1D
h
Number of errors that occurred during data reception at port 1 for those slaves standing in line before the current
slave in bus topology.
Display range (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1096/30 | ECAT: Forwarded Rx error counter - port 2
Data type: UNSIGNED_8
Index: 23479.30
d
=
0x5BB7.0x1E
h
Number of errors that occurred during data reception at port 2 for those slaves standing in line before the current
slave in bus topology.
Display range (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1096/31 | ECAT: Forwarded Rx error counter - port 3
Data type: UNSIGNED_8
Index: 23479.31
d
=
0x5BB7.0x1F
h
Number of errors that occurred during data reception at port 3 for those slaves standing in line before the current
slave in bus topology.
Display range (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1096/32 | ECAT: Error counter processing unit
Data type: UNSIGNED_8
Index: 23479.32
d
=
0x5BB7.0x20
h
Number of errors that occurred in the processing unit.
EtherCAT slave controller error counter register "0x030C": Internal error of the slave
Display range (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1096/33 | ECAT: PDI error counter
Data type: UNSIGNED_8
Index: 23479.33
d
=
0x5BB7.0x21
h
Number of internal errors of the slave, reported by the process data interface.
Display range (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC STOP No transfer
Seitenansicht 187