Technical data
General data and operating conditions
4
27
EDS700ACBA EN 4.0
Environmental conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C) < 6 months
1K3 (−25 ... +40 °C) > 6 months
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +55 °C)
For operation above +40 °C:
l Reduce rated output current by 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl:
l Reduce rated output current by 5 %/1000 m
Pollution EN 61800−5−1 Pollution degree 2
Vibration resistance (9.81 m/s
2
= 1 g)
Transport EN 60721−3−2 2M2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
EN 61800−5−1 10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 10 m/s
2
Germanischer Lloyd general vibration stress characteristic 1
5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
Supply conditions
Power supply modules
AC mains connection
direct connection to an AC system acc. to technical data
Power systems
TT
with an earthed neutral:
l Operation permitted without restrictions.
TN
IT With measures on the supply module operation in IT systems
is permitted ( 99).
Operation on public
supply systems
EN 61000−3−2
Measures for the limitation of harmonic currents at a total
power on the mains > 1 kW:
Operation without additional measures
The compliance with the requirements for the axis grouping
with power supply module and for the machine/plant is the
responsibility of the manufacturer of the machine or system.
Axis modules
DC mains connection
direct connection to a DC system acc. to technical data
l E70ACP... power supply modules
l equivalent DC sources acc. to technical data
Symmetrical DC voltage to PE required.
Earthing of +UG/−UG conductor will destroy the axis
modules.
Motors Only use motors suitable for inverter operation. L−force
motors from Lenze meet the requirements.
Motor cable length £ 50 m
Encoder cable length £ 50 m