4 Technical data
General Data
EDK82ZAFPC-010 DE/EN/FR 6.0
48
H1_Daten-Schutzisolierung_010
4 Technical data
General Data
Field Values
Order designation E82ZAFPC010
PUO ID number 0x00DA
hex
Communication profile
(DIN 19245 part 1 and part 3)
PROFIBUS-DP
Communication medium RS485
Drive profile DRIVECOM profile ”Power Transmission 20”, can be switched off
Network topology
Without repeater: line
With repeater: line or tree
PROFIBUS node Slave
Baud rate [kbps] 9.6 ... 12000 (automatic detection)
Process data words 1 word ... 10 words
(16 bits per word)
DP user data length 4 parameter data words +
1 ... 10 process data words
Max. number of nodes
Standard: 32 (= 1 bus segment)
With repeater: 125
Max. cable length per bus
segment
1000 m (depending on the baud rate and cable type used)
Communication time
Sum of the cycle time and the processing time in the fieldbus
nodes. The times are independent of each other.
Processing time in the controller:
– Parameter data: approx. 30 ms + 20 ms tolerance
– Process data: approx. 3 ms + 2 ms tolerance
External DC voltage supply +24 V DC ±10 %, max. 80 mA