6.3 Signal functions for analog inputs and outputs EPM−T330
Function library LenzeIOSystem.lib
Appendix
6−6
L
LenzeIOSystem.lib EN 1.7
6.3 Signal functions for analog inputs and outputs EPM−T330
Input range (channels 0, 1)
Parameter
bytes 2/3/4/5
Signal function Signal range Format Tolerance
1)
00
h
Parameter data in module not overwritten
3B
h
Voltage measuring
(complement on two)
±10 V
−10.00
−16384
{0.01 V}
{1 dec}
+10.00
+16384
B
±0.2 % of limit value
Lower range limit: −12.50 V
−20480
dec
Upper range limit: +12.50 V
+20480
dec
75
h
Voltage measuring 0...10 V
0.00
0
{0.01 V}
{1 dec}
+10.00
+16384
B
±0.4 % of limit value
Lower range limit: −
Upper range limit: +12.50 V
+20480
dec
28
h
Voltage measuring
(complement on two)
±10 V
−10.00
−27648
{0.01 V}
{1 dec}
+10.00
+27648
A
±0.2 % of limit value
Lower range limit: −11.76 V
−32512
dec
Upper range limit: +11.76 V
+32511
dec
7A
h
Voltage measuring 1 ... 5V
+1.00
0
{0.01 V}
{1 dec}
+5.00
+27648
A
±0.6 % of limit value
Lower range limit: 0.00 V
−6912
dec
Upper range limit: +5.704 V
+32511
dec
7D
h
Voltage measuring 0...10 V
0.00
0
{0.01 V}
{1 dec}
+10.00
+27648
A
±0.4 % of limit value
Lower range limit: −
Upper range limit: +11.76 V
+32511
dec
3A
h
Current measuring
(complement on two)
±20 mA
−20.00
−16384
{0.01 mA}
{1 dec}
+20.00
+16384
B
±0.3 % of limit value
Lower range limit: −25.00 mA
−20480
dec
Upper range limit: +25.00 mA
+20480
dec
76
h
Current measuring 0 ... 20 mA
0.00
0
{0.01 mA}
{1 dec}
+20.00
+16384
B
±0.6 % of limit value
Lower range limit: −
Upper range limit: +25.00 mA
+20480
dec
2C
h
Current measuring
(complement on two)
±20 mA
−20.00
−27648
{0.01 mA}
{1 dec}
+20.00
+27648
A
±0.3 % of limit value
Lower range limit: −23.51 mA
−32512
dec
Upper range limit: +23.51 mA
+32511
dec
2D
h
Current measuring
(complement on two)
4 ... 20 mA
+4.00
0
{0.01 mA}
{1 dec}
+20.00
+27648
A
±0.8 % of limit value
Lower range limit: +1.18 mA
−4864
dec
Upper range limit: +22.81 mA
+32511
dec
Kommentare zu diesen Handbüchern