5 MC1000 RATINGS
The following tables indicate the input and output ratings of the MC1000 Series.
NOTE: The output current ratings are based on operation at carrier frequencies
of 8 kHz and below. At full ambient temperature, operation at carrier frequencies
above 8 kHz require derating the drive by multiplying the output current rating by
the following factors: 0.94 at 10 kHz, 0.89 at 12 kHz, and 0.83 at 14 kHz. Refer
to Parameter 23 - CARRIER in Section 18 - DESCRIPTION OF PARAMETERS.
NOTE
Refer to Appendix A for derated single phase ratings on selected models.
M1100 SERIES RATINGS
MODEL
INPUT OUTPUT
(120/240 Vac, 50 - 60 Hz) (0 - 230 Vac)
MODEL
NUMBER
1
FOR MOTORS NOMINAL NOMINAL
RATED INPUT CURRENT
2
POWER CURRENT POWER
HP kW PHASE (AMPS) (KVA) (AMPS) (KVA)
M1103S 0.25 0.18 1 6.0 / 3.0 0.72 1.4 / 1.4 0.56
M1105S 0.5 0.37 1 9.2 / 4.6 1.1 2.2 / 2.2 0.88
M1110S 1 0.75 1 16.2 / 8.1 1.9 4.0 / 4.0 1.6
M1115S 1.5 1.1 1 21 / 10.4 2.5 5.2 / 5.2 2.1
1
Refer to Section 3 for model number breakdown.
2
Refer to Section 8 for recommended fuse type.