PARAMETER MENU
PARAM.
NUMBER
PARAMETER
NAME
RANGE OF
ADJUSTMENT
FAC TORY
DEFAULT
52
53
54
TB14 OUT
TB15 OUT
RELAY
NONE, RUN, FAULT, /FAULT,
LOCK, @ SPEED, ABOVE #3,
I LIMIT, AUT/MAN, FLWR PR, MIN/
MAX ALARM,
INV MIN/MAX A,
MIN ALARM, INV MIN ALARM,
MAX ALARM, INV MAX ALARM,
REVERSE, SLEEP, SPD = 0HZ
NONE
55 TB5B LOSS FAULT, SP#4, NONE FAULT
57 SERIAL DISABLED, W/TIMER, W/O TIMR DISABLE
58 ADDRESS 1 - 247 30
61 PASSWORD 0000 - 9999 0019
63 SOFTWARE (VIEW - ONLY) (N/A)
64 MONITOR OFF, ON ON
65 PROGRAM
MAINTAIN, RESET 60,
RESET 50 (NOTE 4)
RESET 60
66 HISTORY MAINTAIN, CLEAR MAINTAIN
70 PID MODE OFF, NORMAL, REVERSE OFF
74 PID FB TB-5A, TB-5B TB-5A
75 FB @ MIN -32768 to 32767 0.0 %
76 FB @ MAX -32768 to 32767 100.00 %
77 P GAIN 0.0 - 999.9 % 5.0 %
78 I GAIN 0.0 - 10.0 SEC 0.0 SEC
79 D GAIN 0.0 - 10.0 SEC 0.0 SEC
80 PID ACC 0.0 - 100.0 SEC 30.0 SEC
81 MIN ALRM FB @ MIN - FB @ MAX 0.0 %
82 MAX ALRM FB @ MIN - FB @ MAX 0.0 %
98 LANGUAGE ENGLISH
99 FAULT HISTORY (VIEW - ONLY) (N/A)
NOTE 4: "RST HIGH" WILL APPEAR ON UNITS SET UP FOR HIGH FREQUENCY.
NOTE!
If you are working with Software M108313 or ealier (see Parameter 63),
parameters 69 and 70 are shown here as parameters 98 and 99.