13435742_EDBM101_v24 11
M1200 SERIES RATINGS
MODEL
INPUT OUTPUT
(200/240 Vac, 50 - 60 Hz) (0 - 200/230 Vac)
MODEL
NUMBER
1
FOR MOTORS NOMINAL NOMINAL
RATED INPUT CURRENT
2
POWER CURRENT POWER
HP kW PHASE (AMPS) (KVA) (AMPS) (KVA)
M1205S 0.5 0.37 1 5.8 / 5.0 1.2 2.5 / 2.2 0.9
M1205 0.5 0.37 3 3.1 / 2.7 1.1 2.5 / 2.2 0.9
M1210S 1 0.75 1 10.4 / 9.0 2.2 4.6 / 4.0 1.6
M1210 1 0.75 3 5.5 / 4.8 2.0 4.6 / 4.0 1.6
M1215S 1.5 1.1 1 13.3 / 11.6 2.8 6.0 / 5.2 2.1
M1215 1.5 1.1 3 7.1 / 6.2 2.6 6.0 / 5.2 2.1
M1220S 2 1.5 1 17.1 / 14.9 3.6 7.8 / 6.8 2.7
M1220 2 1.5 3 9.3 / 8.1 3.4 7.8 / 6.8 2.7
M1230S 3 2.2 1 24 / 21 5.0 11.0 / 9.6 3.8
M1230 3 2.2 3 13.0 / 11.3 4.7 11.0 / 9.6 3.8
M1250 5 3.7 3 20 / 17.7 7.4 17.5 / 15.2 6.1
M1275 7.5 5.5 3 30 / 26 10.6 25 / 22 8.8
M12100 10 7.5 3 37 / 32 13.2 32 / 28 11.2
M12150 15 11 3 55 / 48 19.8 48 / 42 16.7
M12200 20 15 3 70 / 61 25.3 62 / 54 21.5
M12250 25 18.5 3 89 / 77 32.0 78 / 68 27.1
M12300 30 22 3 104 / 90 37.6 92 / 80 31.9
M12400
3
40 30 3 119 / 99 41.0 120 / 104 41.4
M12600
3
60 45 3 174 / 145 60.5 177 / 154 61.3
1
Refer to Section 3 for model number breakdown.
2
Refer to Section 8 for recommended fuse type.
3
For branch circuit protection, the 40HP and 60HP 230V models must only be
installed with the appropriately rated UL Listed fuses.