62 13435742_EDBM101_v24
52 TB14 OUT (TB-14 OPEN COLLECTOR OUTPUT)
This parameter sets the open-collector output indication for terminal TB-14.
The following conditions can be selected:
NONE This setting disables the output.
RUN The relay energizes when the drive is given a START command,
and remains energized until: a STOP command is given and
the output frequency has decelerated to 0.5 Hz, the drive has
“tripped”, or the input voltage is removed. Note that this relay
indicates only that the drive is in the RUN mode. It does not
necessarily indicate that the motor is turning.
FAULT The relay energizes when input voltage is applied to the
drive and remains energized until the drive “trips” into a fault
condition, or input voltage is removed.
/ FAULT INVERSE FAULT - The relay energizes when the drive “trips”
into a fault condition, and remains energized until the fault
condition is cleared.
LOCK FAULT LOCKOUT - This relay is used when the drive is
programmed to automatically restart after a fault. The relay
energizes when input voltage is applied to the drive and
remains energized until the drive has faulted and unsuccessfully
attempted ve restarts, or input voltage is removed.
@ SPEED AT SPEED - The relay energizes when the drive reaches the
speed set point. To avoid a “chattering” relay (energizing and
de-energizing), due to small uctuations in speed, the relay will
remain energized as long as the actual speed is within + 0.50
Hz of the speed set point.
ABOVE #3 ABOVE SPEED #3 - The relay energizes when the output
frequency exceeds the SPEED #3 value, and de-energizes
when the output frequency returns to a value lower than the
SPEED #3 value. Refer to Parameter 3 - SPEED #3 in Section
18 - DESCRIPTION OF PARAMETERS.
I LIMIT CURRENT LIMIT - The relay energizes when the drive is
operating in current limit. Once the current limit relay is
energized, it remains energized for a minimum of 500ms,
regardless of whether the drive is still in current limit. At the end
of the 500ms interval, the relay will de-energize if the drive is
no longer in current limit. Refer to Parameter 16 - CURRENT
in Section 18 - DESCRIPTION OF PARAMETERS.
AUT/MAN AUTO/MANUAL MODE - The relay energizes when the drive
is in the AUTOMATIC mode, and de-energizes in the MANUAL
mode. Refer to Section 14.2.5 - SPEED REFERENCE
SELECTION.
FLWR PR FOLLOWER PRESENT - The relay energizes when the analog
input reference signal at TB-5B is greater than 2 mA, and de-
energizes if the signal falls below 2 mA.
REVERSE The relay energizes when Reverse direction is selected, and
de-energizes when Forward direction is selected.