Working with the ApplicationTemplate PackML
Mapping the actual machine structure: Add devices
40
Lenze · ApplicationTemplate PackML · 1.0 EN - 05/2014
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3. Setting the cycle time
The value for the EtherCAT master cycle time has to be defined according to the cycle
time of the quickest task.
The icon in front of the respective device indicates the successful
EtherCAT communication.
Note: The EtherCAT cycle time is to be set to the quickest task cycle time set. In this
ApplicationTemplate PackML, the quickest task cycle time is set to 2 ms, therefore 2000 μs
have to be set here.
If the "Distributed Clocks" option is activated for all controllers and communication is
successful, the EtherCAT Master provides the "DC In-Sync" message: