Lenze DDS Function library Drive Bedienungsanleitung Seite 12

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 103
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 11
2.1.1 Programming fixed setpoints (L_FIXSET)
Function library LenzeDrive.lib
General signal processing
2−2
L
LenzeDrive.lib EN 1.7
2.1 General signal processing
2.1.1 Programming fixed setpoints (L_FIXSET)
You can program up to 15 fixed setpoints with this FB. The addressing of the setpoint that is to be
output is made through the boolean (logic) inputs.
Fixed setpoints can be used, for example, for:
Different set dancer positions in a dancer position control
Different stretch ratios (gearbox factor) when using a speed ratio control with digital frequency
coupling
anSollW1
anSollW15
anSollW2
DMUX
0
3
0
15
bIn1_b
FIXSET1...15
nOut_a
L_FIXSET
nAin_a
bIn2_b
bIn3_b
bIn4_b
Fig. 2−1 Programming fixed setpoints (L_FIXSET)
VariableName DataType SignalType VariableType Note
nAin_a Integer analog VAR_INPUT nAin_a is connected to nOut_a , if (bIn1_b ... bIn4_b)
FALSE is on all the selection inputs.
bIn1_b Bool binary VAR_INPUT
The number of inputs to be assigned depends on the
number of required fixed setpoints.
bIn2_b Bool binary VAR_INPUT
bIn3_b Bool binary VAR_INPUT
bIn4_b Bool binary VAR_INPUT
nOut_a Integer analog VAR_OUTPUT
anSollW[1...15] Array of integers VAR CONSTANT RETAIN Variable that can have fixed setpoints assigned to
them.
Parameter codes of the instances
VariableName L_FIXSET1 SettingRange Lenze
anSollW[1...15] C0560/1 ... 15 −199.99 ... 199.99 % 0.00
Function
nOut_a can be used as a setpoint source (signal source) for another FB (e.g. process controller,
arithmetic block, etc.). The parameterization and handling is the same as for JOG, but it is
independent of JOG. (^ 2−73: L_NSET)
Parameterization of the fixed setpoints
The individual fixed setpoints can be parameterized through anSollW1 ... anSollW15.
Output of the selected fixed setpoint:
If the binary inputs are triggered with a HIGH signal, a fixed setpoint from the table is
switched to nOut_a . (^ 2−3)
Range:
You can enter values from −199.99% ... 199.99% (100 % corresponds to 16384).
Seitenansicht 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 102 103

Kommentare zu diesen Handbüchern

Keine Kommentare