E84AYCEC communication manual (Ethernet POWERLINK)
Parameter reference
Parameters of the communication module
74 L EDS84AYCEC EN 3.0 - 09/2012
C13079
C13102
C13136
Parameter | Name:
C13079 | 0x1F9B Multiplex Cycle CN
Data type: UNSIGNED_8
Index: 11496
d
= 2CE8
h
This code indicates in which multiplexed cycle the node is queried. The value entered must not exceed the value in
code C13074
.
If, for instance, the value "3" is entered in code C13074
, the multiplexed cycle is repeated every three cycles. If now
the value "3" is entered for one node in C13079/x, it is always queried only in the second cycle of the three
multiplexed cycles.
Setting range (min. value | unit | max. value)
0 Cycles 255
Subcodes Lenze setting Info
C13079/1 0 cycles
... ...
C13079/100 0 cycles
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13102 | 0x1F9E NMT Reset Command
Data type: UNSIGNED_8
Index: 11473
d
= 2CD1
h
A reset command to a single EPL node in the network can result in cycle and monitoring errors.
The code initiates a reset of the EPL node.
When the reset has been executed, the code is automatically set to "NoCommand / NMTInvalidService".
Selection list (Lenze setting printed in bold)
40 ResetNode
41 ResetCommunication
42 ResetConfiguration
255 NoCommand
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13136 | SoC Cycle Counter
Data type: UNSIGNED_32
Index: 11439
d
= 2CAF
h
The subcodes of the code display a counter for EPL cycles.
• The SoC cycle counter can be used for activity monitoring.
• The counter is started at "0" each time the EPL node is switched on. The overflow is at "4294967295".
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT