Lenze E84AYCEC Bedienungsanleitung Seite 82

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 89
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 81
E84AYCEC communication manual (Ethernet POWERLINK)
Parameter reference
Table of attributes
82 L EDS84AYCEC EN 3.0 - 09/2012
Table of attributes
Code Name Lenze index Data Access
dec hex DS DA DT Factor R W CINH
C13000
0x1E40.2 IP Address 11575 2D37 A 1 UNSIGNED_32
C13001
0x1E40.3 Subnet Mask 11574 2D36 A 1 UNSIGNED_32
C13003
0x1E40.5 IP Address Router 11572 2D34 A 1 UNSIGNED_32 
C13004
0x1030.5 MAC Address 11571 2D33 A 1 OCTET_STRING
C13028
0x1F81 Node Assignment CN 11547 2D1B A 100 UNSIGNED_32 
C13029
0x1F81 Node Assignment 11546 2D1A A 3 UNSIGNED_32 
C13040
0x1F82 Feature Flags 11535 2D0F E 1 UNSIGNED_32
C13060
0x1006 Cycle Time 11515 2CFB E 1 UNSIGNED_32 1 
C13066
0x1F8D PResPayloadLimit RPDO CN 11509 2CF5 A 100 UNSIGNED_16 1 
C13067
0x1F8D PResPayloadLimit RPDO 11508 2CF4 A 3 UNSIGNED_16 1 
C13071
0x1F98.4 PReqPayloadLimit RPDO 11504 2CF0 E 1 UNSIGNED_16 1 
C13072
0x1F98.5 PResPayloadLimit TPDO 11503 2CEF E 1 UNSIGNED_16 1 
C13074
0x1F98.7 Multiplex Cycle Counter 11501 2CED E 1 UNSIGNED_8 1 
C13075
0x1F98.8 SDO Channel Width
(AsyncMTU)
11500 2CEC E 1 UNSIGNED_16 1 
C13076
0x1F98.9 Prescaler_U16 11499 2CEB E 1 UNSIGNED_16 1 
C13078
0x1F99 BasicEthTimeout 11497 2CE9 E 1 UNSIGNED_32 1 
C13079
0x1F9B Multiplex Cycle CN 11496 2CE8 A 100 UNSIGNED_8 1 
C13102
0x1F9E NMT Reset Command 11473 2CD1 E 1 UNSIGNED_8 1 
C13136
SoC Cycle Counter 11439 2CAF E 1 UNSIGNED_32 1
C13852
PDO word from MN 10723 29E3 A 16 UNSIGNED_16
C13853
PDO words to MN 10722 29E2 A 16 UNSIGNED_16
C13859
0x1A00.0 Number of mapped Tx PDO-
1
10716 29DC A 1 UNSIGNED_8 1
C13860
0x160x.0 Number of mapped Rx PDO 10715 29DB A 6 UNSIGNED_8 1
C13861
0x1F8C NMT Communication Status 10714 29DA E 1 UNSIGNED_8 1
C13864
0x1F93.1 Node ID 10711 29D7 E 1 UNSIGNED_8 1
C13865
0x1F93.2 Node ID by HW 10710 29D6 E 1 UNSIGNED_8 1
C13879
Bus error 10696 29C8 E 1 UNSIGNED_32
C13880
Error reaction 10695 29C7 A 3 UNSIGNED_8 1 
C13884
CU synchronisation active 10691 29C3 E 1 BITFIELD_8
C13885
Error reaction on RPDO check 10690 29C2 E 1 UNSIGNED_8 1 
C13887
Suppress emergency message upon 10688 29C0 E 1 BITFIELD_8 
C13898
0x1F9A Host Name 10677 29B5 E 1 VISIBLE_STRING 
C13899
0x1F93.3 Node ID by SW 10676 29B4 E 1 UNSIGNED_8 1 
C13900
Firmware Type 10675 29B3 E 1 VISIBLE_STRING
C13901
Firmware Date 10674 29B2 E 1 VISIBLE_STRING
C13902
Firmware Version 10673 29B1 E 1 VISIBLE_STRING
C13910
Last Module Error 10665 29A9 E 1 UNSIGNED_32 1 
C13915
CustomerObject[16] 10660 29A4 A 1 OCTET_STRING 
C13920
Current address switch 10655 299F E 1 UNSIGNED_8 1