16 IM94MV01C
2.4.2 RS485 and Modbus
The [RS485 and Modbus] folder contains the configuration parameters of the Modbus interface. Click on any Modbus parameter
to change it. Table 4 lists the range and default value of each RS485 Modbus parameter.
Table 4: RS 485 Modbus Parameters
Parameter Range Default Value
RS 485 Configuration Normal, Modbus slave Normal
Modbus baud rate 2400, 4800, 9600, 19200, 38400, 57600, 115200 19200
Modbus reply delay 0 - 1000ms 0
Modbus parity No Parity, Odd, Even No Parity
Modbus stop bits 1.0, 1.5, 2.0 1.0
2.4.3 CAN
The [CAN] folder contains the configuration parameters for the CAN interface. Click on Parameter name to change the setting
of that parameter. Table 5 lists the range and default value for each CAN parameter.
Table 5: CAN Parameters
Parameter Range Default Value
CAN Control Disabled, CANOpen Simple, CANOpen 402 Disabled
CAN baud rate 10k, 25k, 50k, 125k, 250k, 500k, 800k, 1000k 500k
CAN Address 1 - 127 1
CAN Bootup Mode Pre-operational, Operational, Pseudo master mode Pre-operational
CAN Bootup Delay 0-5 sec 5 sec
2.5 I/O
There are 2 sub-folders under the [I/O] folder in the MotionView Node Tree. The [Digital I/O] folder contains the values of the 4
outputs and debounce times for the 12 inputs. The [Analog I/O] folder contains the values of the one output and one input plus
an action button [Adjust analog input zero offset] that permits the user to change the analog zero offset.
2.5.1 Digital I/O
The [Digital I/O] folder contains the values of the 4 outputs and debounce times for the 12 inputs (A1-A4, B1-B4, C1-C4).
Table 6: Digital Input/Output Parameters
Parameter Range Default Value
Output 1 function Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position
Not assigned
Output 2 function
Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position
Not assigned
Output 3 function Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position
Not assigned
Output 4 function Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position
Not assigned
Input A1 debounce time 0-1000 ms 0
Input A2 debounce time
0-1000 ms 0
Input A3 debounce time 0-1000 ms 0
Input A4 debounce time 0-1000 ms 0
Input B1 debounce time 0-1000 ms 0
Input B2 debounce time
0-1000 ms 0
Input B3 debounce time 0-1000 ms 0
Input B4 debounce time 0-1000 ms 0
Input C1 debounce time 0-1000 ms 0
Input C2 debounce time
0-1000 ms 0
Input C3 debounce time 0-1000 ms 0
Input C4 debounce time 0-1000 ms 0
Hard limit switches action Not assigned, Fault, Stop and fault Not assigned