4 TCF SPECIFICATIONS
Specification Range
Storage Temperature -20° to 70° C
Ambient Operating Temperature 0° to 50° C (derate 2.5% per °C above 50°)
Ambient Humidity < 95% (non-condensing)
Maximum Altitude 3300 ft. (1000 m) above sea level (derate 5% per additional 3300 ft.)
Input Line Voltages 208/240 Vac, 400/480 Vac, 480/590 Vac
Input Voltage Tolerance +10%, -15%
Input Frequency Tolerance 48 to 62 Hz
Output Wave Form Sine Coded PWM
Output Frequency 0 - 240 Hz (consult factory for higher output frequencies)
Carrier Frequency 2 kHz, 4 kHz, 8 kHz (8 kHz requires derating; see parameter P02)
Service Factor 1.00 (up to 4 kHz carrier; derate for 8 kHz; see parameter P02)
Efficiency Up to 98%
Power Factor (displacement) 0.96 or better
Overload Current Capacity 150% for 60 seconds, 200% for 25 seconds
Speed Reference Follower 0-10 VDC, 4-20 mA
Control Voltage 15 VDC
Power Supply for Auxiliary Relays 50 mA at 12 VDC
Analog Output 0 - 10 VDC or 2 - 10 VDC: Proportional to speed, load, or torque
Digital Outputs Open-collector outputs: 50 mA at 30 VDC
Earth Leakage Current < 3.5 mA to earth ground