5 TCF RATINGS
MODEL
NUMBER
(NOTE 1)
FOR MOTORS
RATED
INPUT (50-60 Hz) OUTPUT
HEAT LOSS
(WATTS)
(NOTE 5)
INPUT
PHASE
CURRENT
(AMPS)
POWER
(kVA)
CURRENT
(AMPS)
HP kW
TF200Y SERIES (NOTE 2) 208 / 240 Vac 0 - 200 / 230 Vac
TF205Y 0.5 0.37 1 5.4 / 4.7 1.2 2.5 / 2.2 26
TF205Y 0.5 0.37 3 3.1 / 2.7 1.1 2.5 / 2.2 26
TF210Y 1 0.75 1 10.6 / 9.2 2.2 4.8 / 4.2 49
TF210Y 1 0.75 3 5.8 / 5.1 2.1 4.8 / 4.2 49
TF215Y 1.5 1.1 1 13.9 / 12.0 2.9 6.9 / 6.0 82
TF215Y 1.5 1.1 3 8.0 / 6.9 2.9 6.9 / 6.0 82
TF220Y 2 1.5 1 14.8 / 12.9 3.1 7.8 / 6.8 86
TF220Y 2 1.5 3 9.1 / 7.9 3.2 7.8 / 6.8 86
TF230Y 3 2.2 1 19.7 / 17.1 4.1 11.0 / 9.6 130
TF230Y 3 2.2 3 12.4 / 10.8 4.4 11.0 / 9.6 130
TF200 SERIES (NOTE 2) 208 / 240 Vac 0 - 200 / 230 Vac
TF210 1 0.75 3 5.8 / 5.1 2.1 4.8 / 4.2 41
TF215 1.5 1.1 3 8.0 / 6.9 2.9 6.9 / 6.0 69
TF220 2 1.5 3 9.1 / 7.9 3.3 7.8 / 6.8 78
TF230 3 2.2 3 12.4 / 10.8 4.5 11.0 / 9.6 117
TF250 5 4.0 3 19.6 / 17.1 7.1 17.5 / 15.2 187
TF275 7.5 5.5 3 28 / 25 10.3 25 / 22 286
TF2100 10 7.5 3 34 / 32 13.1 30 / 28 379
NOTE 1: Refer to Section 3 for model number breakdown.
NOTE 2: The higher current ratings are for 208 Vac input and the lower current ratings are for 240 Vac input.
NOTE 5: Values are worst-case (not typical) for 4kHz carrier frequency at full speed and full load.