Lenze TCF Series Bedienungsanleitung Seite 68

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 76
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 67
B APPENDIX - INPUT ASSERTION LEVEL
B.1 GENERAL
Digital inputs on VFDs are asserted or activated by either applying a voltage level to the input
(active-high) or by pulling the input down to a common or ground potential (active-low). This
is an important issue when using solid-state outputs (from an external device) to interface
with the VFD, but is less of an issue when using dry contacts. Most VFDs are set up for either
active-high or active-low, but the TCF can be configured for either type.
The TCF digital inputs (TB-1, 13A, 13B, 13C and 13D) are configured for active-high as
standard. Refer to section B.2 to determine if the assertion level must be changed, depending
on the type of solid-state circuit being used (PNP/sourcing or NPN/sinking).
NOTE
If dry contacts (from relays, switches, push buttons, etc), or PNP/sourcing
circuits are to be used to activate the digital inputs, the assertion level does
not need to be changed, and this Appendix can be ignored. Also, the label
that covers the control terminal strip can be discarded.
Parameter 79 - INPUT ASSERTION LEVEL shows the assertion level of the inputs, and is
either HIGH (01) or LOW (02). This parameter can also be used to change from active-high
to active-low during initial set-up using the procedure described below in section B.3.
When set for active-high (P79 set to HIGH), TB-4 is configured as a +12 VDC source and
the digital inputs are activated when they are at +10 VDC or higher (24 VDC max) relative
to TB-4.
When set for active-low (P79 set to LOW), TB-4 is configured as a 0 VDC common and the
digital inputs (which will be at +12 VDC) are activated when they are at +2 VDC or lower
relative to TB-4.
B.2 SOLID-STATE CIRCUITS
The digital inputs were designed to work with dry contacts (refer to NOTE above), as well as
PNP and NPN type open-collector circuits.
PNP OPEN-COLLECTOR CIRCUITS
If PNP (current-sourcing) outputs are to be
used to activate the drive's digital inputs, the
assertion level does not need to be changed
from the factory default of HIGH.
NPN OPEN-COLLECTOR CIRCUITS
If NPN (current-sinking) outputs are to be
used to activate the drive's digital inputs, the
assertion level must be changed to active-
low. Refer to section B.3 for the procedure to
change P79 to LOW.
TB-4 (+12 VDC)
TCF DIGITAL INPUT (0 VDC)
(ACTIVE-HIGH)
PNP
TB-4 (0 VDC)
TCF DIGITAL INPUT (+12 VDC)
(ACTIVE-LOW)
NPN
64