L
18
How to wire the module
Only use cables according to the following cable specification.
Observe the following illustrations concerning the bus connector.
Make the connection to the controllers using the bus connector.
The bus system is not interrupted if you disconnect the plug from
the controller.
Connect a terminating resistor at the physical bus ends . This
resistor is integrated in the bus connection plug. You can activate it
by using a switch.
If the 2130IB bus interface module is not supplied with power any
more, the bus system continues to operate. The connected
controller, however, cannot be called by the host.
If you want to disconnect individual bus participants, make sure that
the terminating resistors at the physical cable ends remain active.
Further notes and wiring instructions can be obtained from the
documentation of the control manufacturer.
Connection of the bus cable in the bus connector
ON
A
B
A
B
4
5
V
V
1 = 9-pole SubD connector
2 = Guides for the bus cable
3 = Housing screw
4 = Terminating resistor (not connected))
5 = Cable screen; must lay bare
on the metal guide
V
1
2
3
V
V
approx. 6 mm
approx. 11 mm
approx. 11 mm
cable screen
bus cable
V
V
Seitenansicht 19