Lenze EVS9332xS Bedienungsanleitung Seite 138

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 264
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 137
Function library
Function blocks
3.2.31 First order derivative−action element (DT1)
3−86
l
EDSVS9332S−EXT EN 2.0
3.2.31 First order derivative−action element (DT1)
Purpose
Derivative action on signals.
For instance, used for the acceleration processes (dv/dt).
DT1-1
DT1-1-OUT
DT1-1-IN
C0654
C0651
C0652
±199.99 %
C0653
C0650
fb_dt1−1
Fig. 3−80 First order derivative−action element (DT1−1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DT1−1−IN a C0654 dec [%] C0652 1 1000
DT1−1−OUT a Limited to ±199.99 %
Function
l The gain is set under C0650.
l The delay T
v
is set under C0651.
l The input sensitivity of the DT1−1 element can be reduced under C0653.
l The FB only evaluates the specified most significant bits, according to the setting.
t
T
v
K=T
d
/T
v
Fig. 3−81 Delay time T
v
of the first order derivative−action element