
Application examples
4.5 Master frequency bus − slave − drive (C0005 = 6000)
4−12
l
EDSVS9332S−EXT EN 2.0
4.5 Master frequency bus − slave − drive (C0005 = 6000)
Tip!
The most important settings can be found in the menu: "Short Setup / Speed mode" of the operating
module or in the menu "Short setup / Speed mode" in Global Drive Control.
Enter motor type (contains all nameplate data of the motor)
C0173 xxx Enter UG limit (mains voltage)
C0086 000 Enter motor data manually
Enter maximum motor current
C0022 xxxA Determine Imax
Enter controller configuration
C0005 6000 Select digital frequency cascade − slave
C0025 xxx Enter feedback system
Speed setpoint settings
C0011 xxx rpm Determine max. speed
C0032 xxx Numerator of gearbox factor
C0033 xxx Denominator of gearbox factor
C0425 xxx Adjust encoder constant to the master
Application parameters
C0070 xxx Vp n−controller
C0071 xxx Tn n−controller
C0254 xxx Gain of the angle controller
Save parameters
C0003 xxx Save all parameters
Kommentare zu diesen Handbüchern