Drive PLC Developer Studio
Resources
8-37
l DDS EN 2.3
8.9.3.4 Load watch list
Icon: - Menu: ExtrasWLoad watch list Keyboard: -
Use this command to load a saved watch list.
Selection of the command opens the dialog box
Open
.
• Select the required file with the extension ”*.wtc” and click OK.
Enter the new watch list name in the dialog box.
• The input field already displays the file name without extension.
Click Extras➞
➞➞
➞Save watch list to save a watch list.
8.9.3.5 Monitoring active
Icon: - Menu: ExtrasWMonitoring active Keyboard: -
Use this command to switch the display of the Watch and Receipt Manager on and off in online
mode.
• If the display is activated, a tick appears in front of the menu item.
The display must be switched off with this command to enter a new variable or to pre-assign a value.
The display can be switched on again after the variable has been entered, executing the command
again.
8.9.3.6 Write receipt
Icon: - Menu: ExtrasWWrite Receipt Keyboard: -
Use this command to write the pre-assigned values to the variables in the Watch and Receipt
Manager’s online mode.
8.9.3.7 Read Receipt
Icon: - Menu: ExtrasWRead Receipt Keyboard: -
Use this command to replace the pre-assignment of the variables with the current values in the
Watch and Receipt Manager’s online mode.
Example:
PLC_PRG.counter [:= <current value>] = <current value>
Tip!
Only the values in the watch list selected in the Watch and Receipt Manager will be loaded!