Technical data
General data
4
l
16
EDSMF2133IB EN 5.0
4 Technical data
4.1 General data
Area Values
Order designation EMF2133IB
PNO ID number 2133
hex
Communication profile
(DIN 19245 Part 1 and Part3)
l PROFIBUS−DP−V0
l PROFIBUS−DP−V1
Communication medium RS485
Interface 9−pin Sub−D socket
Drive profile l DRIVECOM profile "drive technology 20" (can be switched off)
l PROFIdrive profile (can be switched off, state machine and PROFIdrive
parameter data channel)
Network topology l without repeaters: Line
l with repeaters: Line or tree
PROFIBUS nodes Slave
Baud rate [kbps] 9.6 ... 12000 (automatic detection)
Process data words 1 ... 12 words
(16 bits/word)
DP user data length 1 ... 12 process data words +
4 parameter data words
Max. number of stations l Standard: 32 (= 1 bus segment)
l with repeater: 125
Max. cable length per bus
segment
1200 m (depending on the baud rate and cable type used)
External DC voltage supply V = +24 V DC ±10 %
I = 120 mA
, Documentation for Lenze series of devices 8200 vector, 9300 and ECS
Here you can find the ambient conditions and the electromagnetic
compatibility (EMC) specifications applying to the communication module.