Lenze EMF2133IB Bedienungsanleitung Seite 48

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 134
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 47
Process data transfer
Lenze device control
Process data signals for 82XX frequency inverters
7
l
48
EDSMF2133IB EN 5.0
Device status word AIF−STAT for 82XX (C0150, I−5F69)
820X 821X / 822X / 824X
Bit Assignment Bit Assignment
0
Current parameter set
0
Current parameter set
0
1
Parameter set 1 or 3 active
Parameter set 2 or 4 active
0
1
Parameter set 1 or 3 active
Parameter set 2 or 4 active
1 Pulse inhibit (IMP)
1
Pulse inhibit (IMP)
0
1
Pulses for power stage enabled
Pulses for power stage inhibited
0
1
Pulses for power stage enabled
Pulses for power stage inhibited
2
I
max
(current limit reached)
2
I
max
(current limit reached)
0
1
Current limit not reached
Current limit reached
0
1
Current limit not reached
Current limit reached
3 Not assigned 3
f
d
= f
dset
0
1
f
d
f
dset
f
d
= f
dset
4
f
d
= f
dset
4
Ramp function generator (RFG) on/off
0
1
f
d
f
dset
f
d
= f
dset
0
1
RFG−On RFG−Off
RFG on = RFG off
5
Qmin (f
d
f
dQmin
)
5
Qmin (f
d
f
dQmin
)
0
1
Qmin not active
Qmin active
0
1
Qmin not active
Qmin active
6
f
d
= 0 (actual frequency value = 0)
6
f
d
= 0 (actual frequency value = 0)
0
1
f
d
0
f
d
= 0
0
1
f
d
0
f
d
= 0
7
Controller inhibit (CINH))
7
Controller inhibit (CINH))
0
1
No controller inhibit
Controller inhibit active
0
1
No controller inhibit
Controller inhibit active
8 ... 11 Device status 8 ... 11 Device status
Bit 11 10 9 8 Bit 11 10 9 8
0 0 0 0 Device initialisation 0 0 0 0 Device initialisation
1
0 0 0 Active fault 0 0 1 0 Switch−on inhibit
0 0 1 1 Operation inhibited
0
1 0 0 Flying restart circuit active
0
1 0 1 DC injection brake active
0
1 1 0 Operation enabled
0
1 1 1 Message active
1
0 0 0 Active fault
1
1 1 1 Communication with standard
device not possible
12
Overtemperature warning
12
Overtemperature warning
0
1
No warning
Warning
0
1
No warning
Warning
13
U
Gmax
(DC bus overvoltage)
13
U
Gmax
(DC bus overvoltage)
0
1
No overvoltage
Overvoltage
0
1
No overvoltage
Overvoltage
14
Direction of rotation
14
Direction of rotation
0
1
CW rotation
CCW rotation
0
1
CW rotation
CCW rotation
15
Ready for operation
15
Ready for operation
0
1
Not ready for operation
Ready for operation
0
1
Not ready for operation
Ready for operation